n
Interface networked with
–
Here you can connect the PROFINET interface to the desired subnet.
n
IP protocol
–
Here you can specify the IP address, subnet mask and gateway for the
PROFINET interface.
n
PROFINET
–
Here you can specify a
‘PROFINET device name’
. On the Ethernet subnet, the
‘PROFINET device name’
must be unique. For an integrated PROFINET inter-
face the
‘PROFINET device name’
is derived from the short description. You can
change this at any time.
n
Operating mode
–
You should not change anything here, as the settings for using the PROFINET IO
controller as an I-Device are not relevant.
PROFINET interface - Advanced options
n
Support device replacement without exchangeable medium
–
This parameter is not evaluated. With configured topology the
device replacement
without exchangeable medium
is supported.
PROFINET interface - Advanced options Port ...1
n
Name
–
Here you can change the name of the port, which is also shown in the configura-
tion table.
n
Comment
–
Here you can describe the port in more detail. The comment also appears in the
configuration table.
These parameters serve for the port setting of the topology.
These parameters serve for the port setting. Here the following parameters are sup-
ported:
n
Connection
–
Here you can make settings for transmission medium and type. Ensure that the
setting for the local port and the partner port are identical.
–
PROFINET requires 100Mbps in duplex mode.
n
Boundaries
–
Boundaries
are limitations for the transfer of certain Ethernet frames. The fol-
lowing
Boundaries
are supported:
‘End of detection of accessible nodes’
: DCP frames for detecting accessible
nodes are not forwarded. When enabled, participants which are lying behind this
port, are no longer recognized and can not be reached by the controller.
‘End of topology discovery’
: When activated, this port does not support topology
detection, i.e. the LLDP telegrams are not forwarded.
Ethernet address
Operating mode
Interface Options
General
Port interconnection
Port options
VIPA System SLIO
Configuration with TIA Portal
TIA Portal - Deployment PG/OP communication - PROFINET > Deployment as PROFINET IO controller