Event ID
Description
64: Synchronous cycle interrupt (OB 64)
65: Synchronous technology interrupt (OB 65)
80: Time error OB (OB 80)
81: Power supply error OB (OB 81)
82: Diagnostic interrupt OB (OB 82)
83: Plug/Pull OB (OB 83)
85: Program sequence error OB (OB 85)
86: Component rack failure OB (OB 86)
PK: Priority class
ZINFO1: Logical address of the IO system
ZINFO2: Interrupt reason
0: Unknown
1: Alarm overflow
2: Message box overflow
3: Cyclic data not in bus cycle
4: Application bus cycle error
5: Watchdog
6: Error handler
7: Time-out when receiving cyclic data
8: No not-IO-task available
ZINFO3 - Position 0: Station number
ZINFO3 - Position 11: IO system ID
ZINFO3 - Bit 15: System ID DP/PN
0xE003
Error in access to periphery
ZINFO1: Transfer type
ZINFO2: Periphery address
ZINFO3: Slot
0xE004
Multiple configuration of a periphery address
ZINFO1: Periphery address
ZINFO2: Slot
0xE005
Internal error - Please contact the hotline!
ZINFO1: Not user relevant
ZINFO2: Not user relevant
ZINFO3: Not user relevant
0xE007
Configured input/output bytes do not fit in the periphery area
0xE008
Internal error - Please contact the hotline!
0xE009
Error on accessing the standard backplane bus
0xE010
Non-defined component recognised at the standard backplane bus