![YASKAWA VIPA System SLIO Manual Download Page 123](http://html.mh-extra.com/html/yaskawa/vipa-system-slio/vipa-system-slio_manual_907132123.webp)
5.4 Digital input
5.4.1 Properties
n
16xDC 24V
n
Maximum input frequency
–
10 inputs: 100kHz
–
6 inputs: 1kHz
n
Interrupt functions parameterizable
n
Status indication via LEDs
5.4.2 Wiring
X4
Function
Type
Description
4
DI 0
I
+0.0: Digital input DI 0
5
DI 1
I
+0.1: Digital input DI 1
6
DI 2
I
+0.2: Digital input DI 2
7
DI 3
I
+0.3: Digital input DI 3 *
8
DI 4
I
+0.4: Digital input DI 4 *
9
DI 5
I
+0.5: Digital input DI 5
10
DI 6
I
+0.6: Digital input DI 6 *
11
DI 7
I
+0.7: Digital input DI 7 *
12
DI 8
I
+1.0: Digital input DI 8
13
DI 9
I
+1.1: Digital input DI 9 *
14
DI 10
I
+1.2: Digital input DI 10 *
15
DI 11
I
+1.3: Digital input DI 11 *
16
DI 12
I
+1.4: Digital input DI 12
17
DI 13
I
+1.5: Digital input DI 13
18
DI 14
I
+1.6: Digital input DI 14
19
DI 15
I
+1.7: Digital input DI 15 *
20
DC 24V
I
5L+: DC 24V power section supply for on-board DI
21
0 V
I
5M: GND power section supply for on-board DI
*) Max. input frequency 100kHz otherwise 1kHz.
X4: Connector
VIPA System SLIO
Deployment I/O periphery
Digital input > Wiring
HB300 | CPU | 013-CCF0R00 | en | 19-30
123