5.9.2 Wiring
5.9.2.1
Pulse train outputs
X5
Function
Type
Description
1
Sys DC 24V
I
1L+ DC 24V for electronic section supply
2
Sys 0V
I
1M: GND for electronic section supply
6
DO 0.0
O
Pulse train 0
7
DO 0.1
O
Pulse train 1
18
DC 24V
I
2L+ 24V DC power section supply for pulse train
19
0V
I
2M: GND for pulse train
20
DC 24V
I
3L+: DC 24V SLIO bus power section supply
21
0V
I
3M: GND SLIO bus power section supply
5.9.3 Proceeding
PWM
and
pulse train
output use the same hardware configuration. Switching between
these modes is done within SFB 49. In the Siemens SIMATIC Manager the following
steps should be executed:
1.
Perform a hardware configuration for the CPU.
Chap. 4.5 ‘Hardware configura-
2.
Double-click the counter sub module of the CPU 314C-2 PN/DP.
ð
The dialog
‘Properties’
is opened.
3.
As soon as you select the operating mode for the corresponding channel, a dialog
box with default values for this counter mode is created and shown. For
PWM
respectively
pulse train
output select for the corresponding channel the operating
mode
‘Pulse width modulation - PWM’
.
4.
Perform the required parameter settings.
5.
Safe your project with
‘Station
è
Safe and compile’
.
6.
Transfer your project to your CPU.
X5: Connector
Hardware configuration
VIPA System SLIO
Deployment I/O periphery
Pulse train > Proceeding
HB300 | CPU | 013-CCF0R00 | en | 19-30