![background image](http://html.mh-extra.com/html/yaskawa/vipa-system-slio/vipa-system-slio_manual_907132128.webp)
5.6 Counting
5.6.1 Properties
n
4 channels
n
Various counting modes
–
once
–
continuously
–
periodically
n
Control by the user program via blocks
5.6.2 Wiring
5.6.2.1
Counter inputs
X4
Function
Type
Description
4
DI 0
I
+0.0: Counter 0 (A) *
5
DI 1
I
+0.1: Counter 0 (B) *
7
DI 3
I
+0.3: Counter 1 (A) *
8
DI 4
I
+0.4: Counter 1 (B) *
10
DI 6
I
+0.6: Counter 2 (A) *
11
DI 7
I
+0.7: Counter 2 (B) *
13
DI 9
I
+1.1: Counter 3 (A) *
14
DI 10
I
+1.2: Counter 3 (B) *
15
DI 11
I
+1.3: Gate 3 *
19
DI 15
I
+1.7: Latch 3 *
20
DC 24V
I
5L+: DC 24V power section supply for counter
21
0 V
I
5M: GND power section supply for counter
*) Max. input frequency 100kHz otherwise 1kHz.
The following sensors can be connected
n
24V incremental encoders with two phase-shifted by 90 ° tracks
n
24V pulse encoder with direction signal
n
24V initiator as BERO or beam sensor
X4: Connector
Input signals
VIPA System SLIO
Deployment I/O periphery
Counting > Wiring
HB300 | CPU | 013-CCF0R00 | en | 19-30