![background image](http://html.mh-extra.com/html/yaskawa/vipa-system-slio/vipa-system-slio_manual_907132278.webp)
12.6.2
Analog input
12.6.2.1
Overview
n
2xUx12Bit (0 ... 10V)
n
Sub module
‘AI2’
n
Chap. 5.3 ‘Analog input’ page 120
12.6.2.2
Parametrization in SPEED7 Studio
12.6.2.2.1
‘I/O addresses’
Sub module
Input address
Access
Assignment
AI2
800
WORD
Analog input channel 0 (X4)
802
WORD
Analog input channel 1 (X4)
12.6.2.2.2
‘Parameter’
The analog input part has a filter integrated. The parametrization of the filter happens via
the parameter
‘Filter channel 0/1’
. The default value of the filter is 1000ms. The following
values can be entered:
n
2ms: no filter
n
100ms: small filter
n
1000ms: medium filter
n
10000ms: maximum filter
12.6.3
Digital input
12.6.3.1
Overview
n
16xDC 24V
n
Sub module
‘DI16/DO12’
n
Chap. 5.4 ‘Digital input’ page 123
12.6.3.2
Parametrization in SPEED7 Studio
12.6.3.2.1
‘I/O addresses’
Sub module
Input address
Access
Assignment
DI16/DO12
136
BYTE
Digital input I+0.0 ... I+0.7 (X4)
137
BYTE
Digital input I+1.0 ... I+1.7 (X4)
12.6.3.2.2
‘Inputs’
Here you can specify a hardware interrupt for each input for the corresponding edge. The
hardware interrupt is disabled, if nothing is selected (default setting). A diagnostics inter-
rupt is only supported with
Hardware interrupt lost
.
‘Filtering channel 0/1’
‘Trigger for process
interrupt’
VIPA System SLIO
Configuration with VIPA SPEED7 Studio
Deployment I/O periphery > Digital input
HB300 | CPU | 013-CCF0R00 | en | 19-30
278