![YASKAWA VIPA System SLIO Manual Download Page 282](http://html.mh-extra.com/html/yaskawa/vipa-system-slio/vipa-system-slio_manual_907132282.webp)
Output
Description
Assignment
Characteristics of the output The output and the "Comparator" (STS_CMP) status bit
are set, dependent on this parameter.
n
No comparison: The output is used as normal output
and STS_CMP remains reset.
n
Comparator
–
Counter value
³
Comparison value
–
Counter value
£
Comparison value
n
Pulse at
comparison value
–
To adapt the used actuators you can specify a
pulse duration
. The output is set for the specified
pulse duration
when the counter value reaches the
comparison value
. When you've set a main
counting direction the output is only set at reaching
the
comparison value
from the main counting direc-
tion.
No comparison
Pulse duration
Here you can specify the
pulse duration
for the output
signal.
n
The
pulse duration
starts with the setting of the
according digital output.
n
The inaccuracy of the
pulse duration
is less than 1ms.
n
There is no past triggering of the
pulse duration
when
the
comparison value
has been left and reached again
during pulse output.
n
If the
pulse duration
is changed during operation, it will
take effect with the next pulse.
n
If the
pulse duration
= 0, the output is set until the com-
parison condition is not longer fulfilled.
Range of values: 0...510ms in steps of 2ms
0
Frequency
Description
Assignment
Max. counting frequency
Specify the max. frequency for track A/pulse,
track B/direction, Latch and HW gate
60kHz
Frequency
shortest permissible count pulse
1kHz
400
µ
s
2kHz
200
µ
s
5kHz
80
µ
s
10kHz
40
µ
s
30kHz
13
µ
s
60kHz
6.7
µ
s
100kHz
4
µ
s
VIPA System SLIO
Configuration with VIPA SPEED7 Studio
Deployment I/O periphery > Counter
HB300 | CPU | 013-CCF0R00 | en | 19-30
282