5.
Set in the register MPI the transfer parameters of your MPI net and type a valid
address.
6.
Switch to the register
Local connection
.
7.
Set the COM port of the PCs and the transfer rate 38400baud for the MPI program-
ming cable from VIPA.
8.
Transfer your project via
‘PLC
è
Load to module’
via MPI to the CPU and save it
with
‘PLC
è
Copy RAM to ROM’
on a memory card if one is plugged.
To switch the interface X3 MPI(PtP) to PROFIBUS functionality you have
to activate the according bus functionality by means of a VSC storage
media from VIPA. By plugging the VSC storage card and then an overall
reset the according functionality is activated.
1.
Connect your PC to the MPI(PtP) jack X3 of your CPU via a MPI programming
cable.
2.
Load your project in the Siemens SIMATIC Manager.
3.
Choose in the menu
‘Options
è
Set PG/PC interface’
.
4.
Select in the according list the "PC Adapter (PROFIBUS)"; if appropriate you have
to add it first, then click at [Properties].
5.
Set in the register PROFIBUS the transfer parameters of your PROFIBUS net and
enter a valid
PROFIBUS address
. The
PROFIBUS address
must be assigned to the
DP master by a project before.
6.
Switch to the register
Local connection
.
7.
Set the COM port of the PCs and the transfer rate 38400baud for the MPI program-
ming cable from VIPA.
8.
Transfer your project via
‘PLC
è
Load to module’
via PROFIBUS to the CPU and
save it with
‘PLC
è
Copy RAM to ROM’
on a memory card if one is plugged.
Transfer via PROFIBUS is available by DP master, if projected as master
and assigned with a PROFIBUS address before. In slave operation you
have also to enable the option ‘Test , Commissioning, Routing ’ when
selecting the slave mode.
4.10.2
Transfer via Ethernet
So that you may access the according Ethernet interface you have to assign IP address
parameters by means of the "initialization".
n
X1/X2: Ethernet PG/OP channel
–
Chap. 4.7 ‘Hardware configuration - Ethernet PG/OP channel’ page 72
1.
For the transfer, connect, if not already done, the appropriate Ethernet port to your
Ethernet.
2.
Open your project with the Siemens SIMATIC Manager.
3.
Set via
‘Options
è
Set PG/PC Interface’
the access path to "TCP/IP
®
Network
card .... ".
Proceeding Transfer via
PROFIBUS interface
Initialization
Transfer
VIPA System SLIO
Deployment CPU 013-CCF0R00
Project transfer > Transfer via Ethernet
HB300 | CPU | 013-CCF0R00 | en | 19-30