![YASKAWA VIPA System SLIO Manual Download Page 73](http://html.mh-extra.com/html/yaskawa/vipa-system-slio/vipa-system-slio_manual_907132073.webp)
The initialization via PLC functions takes place with the following proceeding:
Determine the current Ethernet (MAC) address of your Ethernet PG/OP channel.
This can be found at the front of your CPU with the name "MAC PG/OP: ...".
X1 PG/OP
X2 PG/OP
MAC PG/OP: 00-20-D5-77-05-10
You get valid IP address parameters from your system administrator. The assignment of
the IP address data happens online in the Siemens SIMATIC Manager starting with ver-
sion V 5.5 & SP2 with the following proceeding:
1.
Start the Siemens SIMATIC Manager and set via
‘Options
è
Set PG/PC interface’
the access path to
‘TCP/IP -> Network card ....’
.
2.
Open with
‘PLC
è
Edit Ethernet Node n’
the dialog window with the same name.
3.
To get the stations and their MAC address, use the [Browse] button or type in the
MAC Address. The Mac address may be found at the 1. label beneath the front flap
of the CPU.
4.
Choose if necessary the known MAC address of the list of found stations.
5.
Either type in the IP configuration like IP address, subnet mask and gateway.
6.
Confirm with [Assign IP configuration].
ð
Direct after the assignment the Ethernet PG/OP channel may be reached online
by these address data. The value remains as long as it is reassigned, it is over-
written by a hardware configuration or an factory reset is executed.
4.7.1 Take IP address parameters in project
From firmware version V2.4.0 and up, you have the following options for configuring the
Ethernet PG/OP channel:
n
Configuration via integrated CPU interface (firmware version V2.4.0 and up only).
n
Configuration via additional CP (all firmware versions).
"Initialization" via PLC
functions
Assign IP address
parameters
2 variants for configura-
tion
VIPA System SLIO
Deployment CPU 013-CCF0R00
Hardware configuration - Ethernet PG/OP channel > Take IP address parameters in project
HB300 | CPU | 013-CCF0R00 | en | 19-30