The assignment of IP address data takes place via the MAC address. The IP address of
your Ethernet PG/OP channel for the interfaces X1 and X2 can be found on the front of
your CPU with the name "MAC PG/OP: ...".
X1 PG/OP
X2 PG/OP
MAC PG/OP: 00-20-D5-77-05-10
The assignment of the IP address data happens online in the Siemens TIA Portal with the
following proceeding:
1.
Start the Siemens TIA Portal.
2.
Switch to the
‘Project view’
.
3.
Click in the
‘Project tree’
at
‘Online access’
and choose here by a doubleclick your
network card, which is connected to the Ethernet PG/OP channel.
4.
To get the stations and their MAC address, use the
‘Accessible device’
. This can
be found at the front of the CPU labelled as "MAC PG/OP: ...".
5.
Choose from the list the module with the known MAC address (Onboard PG/OP
[MAC address]) and open with "Online & Diagnostics" the diagnostics dialog in the
Project area.
6.
Navigate to
Functions > Assign IP address
. Type in the IP configuration like IP
address, subnet mask and gateway.
7.
Confirm with [Assign IP configuration].
ð
Directly after the assignment the Ethernet PG/OP channel is online reachable
using the set IP address data. The value remains as long as it is reassigned, it
is overwritten by a hardware configuration or an factory reset is executed.
"Initialization"
"Initialization"
VIPA System SLIO
Configuration with TIA Portal
TIA Portal - Hardware configuration - Ethernet PG/OP channel
HB300 | CPU | 013-CCF0R00 | en | 19-30