![background image](http://html.mh-extra.com/html/yaskawa/vipa-system-slio/vipa-system-slio_manual_907132352.webp)
Event ID
Description
DatID: Device
0xEA68
PROFINET IO controller: Error writing dataset
OB: Rack/slot of the controller
PK: Error type
0: Dataset error local
1: Dataset error stack
2: Dataset error station
ZINFO1: Dataset number
ZINFO2: Dataset handle (caller)
ZINFO3: Internal error code from PN stack
DatID: Device
0xEA69
Internal error - Please contact the hotline!
ZINFO1: Minimum version for the FPGA
ZINFO2: Loaded FPGA version
0xEA6A
PROFINET IO controller: Service error in the communication stack
OB: Service ID
PK: Rack/slot
ZINFO1: ServiceError.Code
ZINFO2: ServiceError.Detail
ZINFO3 - Position 0: ServiceError.AdditionalDetail
ZINFO3 - Position 8: ServiceError.AreaCode
0xEA6B
PROFINET IO controller: Incorrect Vendor-ID
OB: Operating mode
0: Configuration in operating condition RUN
1: STOP (update)
2: STOP (memory reset)
3: STOP (auto initialization)
4: STOP (internal)
5: STARTUP (cold start)
6: STARTUP (restart/warm start)
7: STARTUP (hot restart)
9: RUN
10: HALT
11: COUPLING
12: UPDATING
13: DEFECTIVE
14: Error search mode
15: De-energised
VIPA System SLIO
System specific event IDs
HB300 | CPU | 013-CCF0R00 | en | 19-30
352