Command
Description
Diagnostics
entry
OPCUA_PGOP_ENABLE
Enable
OPC UA
project via Ethernet PG/OP channel
0xE830
OPCUA_PGOP_DISABLE
Disable
OPC UA
project via Ethernet PG/OP channel
0xE831
*) After a power cycle or loading a hardware configuration, the settings are retained. With
reset to the factory settings
or
over all reset
, the
WebVisu
project is set to the default value "enabled".
The structure of a command file is shown in the following. The corresponding diagnostics
entry is put in parenthesizes.
Example 1
CMD_START
Marks the start of the command sequence (0xE801)
LOAD_PROJECT proj.wld
Execute an overall reset and load "proj.wld" (0xE805)
WAIT1SECOND
Wait ca. 1s (0xE803)
DIAGBUF
Store diagnostics buffer of the CPU as "diagbuff.txt" (0xE80B)
CMD_END
Marks the end of the command sequence (0xE802)
... arbitrary text ...
Text after the command CMD_END is not evaluated.
Example 2
CMD_START
Marks the start of the command sequence (0xE801)
LOAD_PROJECT proj2.wld
Execute an overall reset and load "proj2.wld" (0xE805)
WAIT1SECOND
Wait ca. 1s (0xE803)
WAIT1SECOND
Wait ca. 1s (0xE803)
IP parameter (0xE80E)
SET_NETWORK 172.16.129.210,255.255.224.0,172.16.129.210
WAIT1SECOND
Wait ca. 1s (0xE803)
WAIT1SECOND
Wait ca. 1s (0xE803)
DIAGBUF
Store diagnostics buffer of the CPU as "diagbuff.txt" (0xE80B)
CMD_END
Marks the end of the command sequence (0xE802)
... arbitrary text ...
Text after the command CMD_END is not evaluated.
The parameters IP address, subnet mask and gateway may be received
from the system administrator. Enter the IP address if there is no gateway
used.
Examples
VIPA System SLIO
Deployment CPU 013-CCF0R00
CMD - auto commands
HB300 | CPU | 013-CCF0R00 | en | 19-30