5.7 H: Terminal Functions
5.7 H: Terminal Functions
H parameters are used to assign functions to the external terminals.
◆
H1: Multi-Function Digital Inputs
■
H1-01 to H1-08: Functions for Terminals S1 to S8
These parameters assign functions to the multi-function digital inputs. The various functions and their settings are listed
below in
.
Table 5.35 Multi-Function Digital Input Terminal Settings
Setting 0: 3-Wire Sequence
When one of the digital inputs is programmed for 3-wire control, that input becomes a forward/reverse directional input,
S1 becomes the Run command input, and S2 becomes the Stop command input.
The drive will start the motor when the input S1 set for the Run command is closed for longer than 2 ms. The drive will
stop the operation when the Stop input S2 is released. Whenever the input programmed for 3 wire sequence is open, the
drive will be set for forward direction. If the input is closed, the drive is set for reverse direction.
Note:
When 3-wire sequence is selected, the Run and Stop commands must be input via S1 and S2.
No.
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).
Parameter Name
Setting
Range
Default
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
1 to 9F
40 (F)
: Forward Run Command (2-wire sequence)
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
1 to 9F
41 (F)
: Reverse Run Command (2-wire sequence)
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
0 to 9F
24: External Fault (N.O., always detected, coast to stop)
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
0 to 9F
14: Fault Reset
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
0 to 9F
3 (0)
: Multi-Step Speed Reference 1
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
0 to 9F
4 (3)
: Multi-Step Speed Reference 2
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
0 to 9F
6 (4)
: Jog Reference Selection
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
0 to 9F
8: External Baseblock Command
Setting
Function
Page
Setting
Function
Page
0
3-wire sequence
20 to 2F
External fault
1
Local/remote selection
30
PID integral reset
2
External reference 1/2 selection
31
PID integral hold
3
Multi-Step Speed Reference 1
32
Multi-step speed reference 4
4
Multi-Step Speed Reference 2
34
PID soft starter cancel
5
Multi-Step Speed Reference 3
35
PID input level selection
6
Jog reference selection
40
Forward run command (2-wire sequence)
7
Accel/decel time selection 1
41
Reverse run command (2-wire sequence)
8
Baseblock command (N.O.)
42
Run command (2-wire sequence 2)
9
Baseblock Command (N.C.)
43
FWD/REV command (2-wire sequence 2)
A
Accel/decel ramp hold
44
Offset frequency 1
B
Drive overheat alarm (oH2)
45
Offset frequency 2
C
Analog terminal input selection
46
Offset frequency 3
D
PG encoder disable
47
Node setup
E
ASR integral reset
60
DC Injection Braking command
F
Through mode
61
External Speed Search command 1
10
Up command
62
External Speed Search command 2
11
Down command
63
Field Weakening
12
Forward jog
67
Communications test mode
13
Reverse jog
6A
Drive enabled
14
Fault reset
71
Speed/Torque Control switch
15
Fast Stop (N.O.)
72
Zero Servo
16
Motor 2 selection
75
Up 2 command
17
Fast Stop (N.C.)
76
Down 2 command
18
Timer function input
77
ASR gain switch
19
PID disable
78
External torque reference polarity inversion
1A
Accel/decel time selection 2
7E
Forward/reverse detection (V/f control with simple PG)
1B
Program lockout
90 to 97
DriveWorksEZ Digital input 1 to 8
1E
Reference sample hold
9F
DriveWorksEZ disabled