5.7 H: Terminal Functions
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
291
5
Setting E: Motor temperature
In addition to motor overload fault detection oL1, it is possible to use a PTC (Positive Temperature Coefficient)
thermistor for motor insulation protection.
Refer to Motor Protection Using a Positive Temperature Coefficient (PTC)
Setting F, 1F: Through mode
When set to F or 1F, an input does not affect any drive function, but the input level can still be read out by a PLC via a
communication option or MEMOBUS/Modbus communications.
Setting 10, 11, 12, 15: Forward, Reverse, Regenerative, General torque limit (OLV, CLV, AOLV/PM, CLV/PM)
These functions can be used to set a torque limit using analog inputs for different operating conditions. Refer to
for details.
Setting 13: Torque Limit Using Torque Reference/Speed Limit
When using Torque Control, an analog input programmed to this function can set the torque reference (when in Torque
Control) or the torque limit (when in Speed Control). Refer to
Setting the Torque Reference, Speed Limit, and Torque
Compensation Values on page 239
for details.
Setting 14: Torque compensation
Used to set a torque compensation value when using Torque Control. Refer to
Setting the Torque Reference, Speed
Limit, and Torque Compensation Values on page 239
Setting 16: Differential PID Feedback
If an analog value is set for this function, the PID controller is set for differential feedback. The subtraction of the PID
feedback input value and the differential feedback input value builds the feedback value that is used to calculate the PID
input.
Refer to PID Feedback Input Methods on page 203
Setting 30, 31, 32: DriveWorksEZ Analog Input 1, 2, 3
These settings are for functions used in DriveWorksEZ. Normally there is no need to change or apply these settings.
◆
H4: Multi-Function Analog Outputs
These parameters assign functions to analog output terminals FM and AM for monitoring a specific aspect of drive
performance.
■
H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection
Sets the desired drive monitor parameter U
-
to output as an analog value via terminal FM and AM.
for a list of all monitors. The “Analog Output Level” column indicates if a monitor can be used
for analog output.
Example: Enter “103” for U1-03.
A setting of 031 or 000 applies no drive monitor to the analog output. With this setting, terminal functions as well as FM
and AM output levels can be set by a PLC via a communication option or MEMOBUS/Modbus (through mode).
■
H4-02, H4-03: Multi-Function Analog Output Terminal FM Gain and Bias
H4-05, H4-06: Multi-Function Analog Output Terminal AM Gain and Bias
Parameter H4-02 and H4-05 set the terminal FM and AM output signal level equal to 100% of the monitor (gain).
Parameter H4-03 and H4-06 set the bias added to the monitor output for terminals FM and AM. Both are set as a
percentage, where 100% equals 10 Vdc analog output. The output voltage of both terminals is limited to 10 Vdc.
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc using parameter H4-07 and H4-08.
illustrates how gain and bias settings work.
No.
Name
Setting Range
Default
H4-01
Multi-Function Analog Output Terminal FM Monitor Selection
000 to 999
102
H4-04
Multi-Function Analog Output Terminal AM Monitor Selection
000 to 999
103
No.
Name
Setting Range
Default
H4-02
Multi-Function Analog Output Terminal FM Gain
-999.9 to 999.9%
100.0%