5.7 H: Terminal Functions
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
295
5
■
H6-06: Pulse Train Monitor Selection
Selects the monitor to output as a pulse train signal via terminal MP. Indicate which monitor to output entering the three
digits in U
-
.
Refer to U: Monitors on page 522
for a complete list of monitors. Monitors that can be selected by
H6-06 appear in the table below.
■
H6-07: Pulse Train Monitor Scaling
Pulse train monitor scaling sets the output pulse frequency at terminal MP when the specified monitor item is at 100%.
Set H6-06 to 102 and H6-07 to 0 to make the pulse train monitor output synchronous to the output frequency.
■
H6-08: Pulse Train Input Minimum Frequency
Sets the minimum output frequency that can be detected by the pulse train input. Increasing this setting reduces the time
the drive needs to react to changes in the input signal.
• If the pulse input frequency falls below this level, the pulse input value will be 0.
• Enabled when H6-01 = 0, 1, or 2.
• When simple speed feedback in V/f Control is set as the function for terminal RP (H6-01 = 3), the minimum frequency
becomes the detection time for PG disconnect (F1-14).
No.
Name
Setting Range
Default
H6-06
<1> Set “000” or “031” when the terminal is not used, or when using the terminal in the through mode.
Pulse Train Monitor Selection
000
, 031
, 101, 102, 105, 116,
501, 502, 801 to 809
102
No.
Name
Setting Range
Default
H6-07
Pulse Train Monitor Scaling
0 to 32000 Hz
1440 Hz
No.
Name
Setting Range
Default
H6-08
Pulse Train Input Minimum Frequency
0.1 to 1000.0 Hz
0.5 Hz