3.9 Control Circuit Wiring
102
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
◆
Control Circuit Terminal Block Functions
Drive parameters determine which functions apply to the multi-function digital inputs (S1 to S8), multi-function digital
outputs (M1 to M6), multi-function photocoupler outputs (P1, P2), multi-function analog inputs (A1 to A3), and
multi-function analog monitor outputs (FM, AM). The default setting is listed next to each terminal in
and
.
WARNING!
Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive
with untested control circuits could result in death or serious injury.
WARNING!
Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Setting
parameter A1-06 may change the I/O terminal function automatically from the factory setting.
Refer to Application Selection on
. Failure to comply may result in death or serious injury.
■
Input Terminals
lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
input.
Table 3.10 Control Circuit Input Terminals
Type
<1> Terminal SP and SN are available in CIMR-UB
only.
<2> Setting jumper S3 for an external power supply makes the wire link between terminals H1, H2, and H2 ineffective. Remove the wire link and
connect an external power supply that can supply terminals H1, H2, and HC continuously.
No.
Terminal Name (Function)
Function (Signal Level) Default Setting
Page
Multi-Function Digital Inputs
S1
Multi-function input 1 (Closed: Forward run, Open: Stop)
Photocoupler
24 Vdc, 8 mA
Set the S3 jumper to select between sinking, sourcing mode, and the
power supply. Refer to
Sinking/Sourcing Mode for Digital Inputs
.
S2
Multi-function input 2 (Closed: Reverse run, Open: Stop)
S3
Multi-function input 3 (External fault, N.O.)
S4
Multi-function input 4 (Fault reset)
S5
Multi-function input 5 (Multi-step speed reference 1)
S6
Multi-function input 6 (Multi-step speed reference 2)
S7
Multi-function input 7 (Jog reference)
S8
Multi-function input 8 (Baseblock command (N.O.))
SC
Multi-function input common
Multi-function input common
SP
Digital input power 24 Vdc
Terminal SP and SN are available in CIMR-UB
only.
24 Vdc power supply for digital inputs, 150 mA max (only when not
using digital input option DI-A3)
NOTICE:
Do not jumper or short terminals SP and SN. Failure
to comply will damage the drive.
SN
Digital input power supply 0 V
Safe Disable Inputs
H1
Safe Disable input 1
24 Vdc, 8 mA
One or both open: Output disabled
Both closed: Normal operation
Internal impedance: 3.3 k
Ω
Off time of at least 1 ms
Disconnect the wire jumpers shorting terminals H1, H2, and HC to
use the Safe Disable inputs. Set the S3 jumper to select between
sinking, sourcing mode, and the power supply as explained for
multi-function input terminals in
Sinking/Sourcing Mode Selection
for Safe Disable Inputs (CIMR-UB
H2
Safe Disable input 2
HC
Safe Disable function common
Safe disable function common
Analog Inputs / Pulse Train Input
RP
Multi-function pulse train input (Frequency reference)
Input frequency range: 0 to 32 kHz
Signal Duty Cycle: 30 to 70%
High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc
Input impedance: 3 k
Ω
+V
Power supply for analog inputs
10.5 Vdc (max allowable current 20 mA)
-V
Power supply for analog inputs
-10.5 Vdc (max allowable current 20 mA)
–
A1
Multi-function analog input 1 (Frequency reference bias)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k
Ω
)
A2
Multi-function analog input 2 (Frequency reference bias)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k
Ω
)
4 to 20 mA, 0 to 20 mA (input impedance: 250
Ω
)
Voltage or current input must be selected by DIP switch S1 and H3-09
A3
CIMR-UA
/UD
/UT
:
Multi-function analog input 3 (auxiliary frequency
reference)
CIMR-UB
:
Multi-function analog input 3 (auxiliary frequency
reference) / PTC Input
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k
Ω
)
Use DIP switch S4 on the terminal board to select between analog and
PTC input in CIMR-UB
.
AC
Frequency reference common
0 V
E (G)
Ground for shielded lines and option cards
–
–