![YASKAWA U1000 Series Technical Manual Download Page 591](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114591.webp)
D.2 European Standards
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
591
St
and
ar
ds
Comp
lia
nce
D
◆
EMC Guidelines Compliance for CIMR-U
4
0477
to 4
0930
Drives with stand-alone EMC filters (CIMR-U
4
0477
to 4
0930
) are tested according to European
standards IEC/EN 61800-3: 2004/A1: 2012 and complies with EMC guidelines. Use drives with stand-alone EMC filters
to comply with EMC guidelines.
■
EMC Filter Installation
Installation Method
Verify the following installation conditions to ensure that other devices and machinery used in combination with this
drive (CIMR-U
4
0477
to 4
0930
) also comply with EMC guidelines. Refer to
for EMC filter selection.
1.
Install an EMC filter to the input side specified by Yaskawa for compliance with European standards.
2.
Place the drive in the enclosure.
3.
Use braided shield cable for the drive and motor wiring, or run the wiring through a metal conduit.
4.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
5.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
WARNING!
Electrical Shock Hazard.
Because the leakage current exceeds 3.5 mA in models CIMR-U
4
0302 and larger, IEC/EN 61800-5-1 states that either the power
supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing
conductor with a cross-section of at least 10 mm
2
(Cu) or 16 mm
2
(Al) must be used. Failure to comply may result in death or serious
injury.
Figure D.5
Figure D.5 Ground Area
Figure D.6
Figure D.6 Wiring Diagram for EMC (4
0477, 4
0590)
A – Braided shield cable
C – Cable clamp (conductive)
B – Metal panel
C
B
A
YEC_common
IM
U/T1
W/T2
W/T3
R/L1
S/L2
T/L3
PE
CIMR-U
4
0477, 4
0590
ELCB
(MCCB)
EMC filter
Three-phase
power supply
Motor
Ground
shielded line
main circuit terminal
control circuit terminal
YEC_common