3.9 Control Circuit Wiring
3
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
99
3.9 Control Circuit Wiring
◆
Control Circuit Connection Diagram
Figure 3.35
Figure 3.34 Control Circuit Connection Diagram (example: CIMR-UA2
0028/UD2
0028/UT2
0028)
<1> This figure shows an example of a sequence input to S1 through S8 using a non-powered relay or an NPN transistor. Use jumper S3 to
select the sink mode or the source mode, and internal or external power supply.
<2> Wire the fault relay output separately from the main circuit power supply and other power lines.
<3> The maximum output current capacity for the +V and -V terminals on the control circuit is 20 mA. Never short terV, -V, and
AC, as this can cause erroneous operation or damage the drive.
<4> Set DIP switch S1 to select between a voltage or current input signal to terminal A2. The default setting is for current input.
<5> Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position.
<6> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not intended for
use as a feedback-type of signal.
<7> The sink/source setting for the Safe Disable input is the same as with the sequence input.
CN500
CN500
+
−
+
+
+
−
+
−
Harmonic Filter Module
+
−
+
+
+
−
+
−
S
1
S
2
S
3
S
4
S
5
S
6
S
7
MP
DM
DM
RP
A
1
A
2
A
3
0 V
AC
R
R
S
S
IG
H
1
H
2
HC
Drive
2 k
Ω
S
8
SC
FM
AM
0 V
0 V
AC
FM
AM
AC
E (G)
S
1
S
2
<7>
<3>
<5>
<8>
<6>
<2>
<6>
<4>
<3>
V
I
+
24 V
+
V
MA
M
1
M
2
P
1
P
2
MB
MC
PC
CN5-C
CN5-B
CN5-A
Forward Run / Stop
Reverse Run / Stop
External fault
Fault reset
Multi-speed step 1
Multi-speed step 2
External Baseblock
Jog speed
Multi-function
digital inputs
(default setting)
Sink / Source mode
selection jumper S3
(default: Sink)
Option board
connectors
Pulse Train Input (max 32 kHz)
Shield ground terminal
Multi-function
analog/ pulse
train inputs
Power 10.5 Vdc, max. 20 mA
Analog Input 1
(Frequency Reference Bias)
0 to +10 Vdc (20 k
Ω
)
Analog Input 2
(Frequency Reference Bias)
0 to +10 Vdc (20 k
Ω
)
4 to 20 mA / 0 to 20 mA (250
Ω
)
Analog Input 3
(Aux. frequency reference)
0 to +10 Vdc (20 k
Ω
)
−
V
Power supply, -10.5 Vdc, max. 20 mA
Safety
switch
MEMOBUS/Modbus
comm. RS-422/RS-485
max. 115.2 kbps
Safe Disable inputs
Wire
jumper
Open
Safety relay /
controller
Termination resistor
(120
Ω
, 1/2 W)
DIP
Switch S2
DIP Switch S1
Fault relay output
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function relay output
(During Run)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function photo coupler output 1
(Zero Speed)
48 Vdc, max 50 mA
Multi-function photo coupler output 2
(Speed Agree 1)
48 Vdc, max 50 mA
Multi-function pulse train output
(Output frequency)
0 to 32 kHz (2.2 k
Ω
)
Multi-function analog output 1
(Output frequency)
-10 to +10 Vdc (2mA)
Multi-function analog output 2
(Output current)
-10 to +10 Vdc (2mA)
EDM (Safety Electronic Device Monitor)
Control Circuit
shielded line
twisted-pair shielded line
main circuit terminal
control circuit terminal
<1>
0 V
24 V
24
0
FE
24 V Control Power Supply
Unit Terminals
<9>
SIEP_C710636_02B_1_0.book 99 ページ 2015年11月25日 水曜日 午後4時56分