B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
507
t
B
■
H6: Pulse Train Input/Output
No.(Addr.)
Name
Description
Setting
Page
H6-01
(42CH)
Pulse Train Input Terminal RP
Function Selection
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: V/f Control with Simple PG feedback (possible only when using motor 1 in V/f Control)
Default: 0
Min: 0
Max: 3
H6-02
(42DH)
Pulse Train Input Scaling
Sets the terminal RP input signal frequency that is equal to 100% of the value selected in H6-01.
Default: 1440 Hz
Min: 100 Hz
Max: 32000 Hz
H6-03
(42EH)
Pulse Train Input Gain
Sets the level of the value selected in H6-01 when a frequency with the value set in H6-02 is
input.
Default: 100.0%
Min: 0.0%
Max: 1000.0%
H6-04
(42FH)
Pulse Train Input Bias
Sets the level of the value selected in H6-01 when 0 Hz is input.
Default: 0.0%
Min: -100.0%
Max: 100.0%
H6-05
(430H)
Pulse Train Input Filter Time
Sets the pulse train input filter time constant.
Default: 0.10 s
Min: 0.00 s
Max: 2.00 s
H6-06
(431H)
Pulse Train Monitor Selection
Select the pulse train monitor output function (value of the
-
part of U
-
).
Example: To select U5-01, set “501”.
Default: 102
Min: 000
Max: 809
H6-07
(432H)
Pulse Train Monitor Scaling
Sets the terminal MP output signal frequency when the monitor value is 100%. As an example,
have the pulse train monitor output equal the output frequency, set H6-06 to 102 and H6-07 to 0.
Default: 1440 Hz
Min: 0 Hz
Max: 32000 Hz
H6-08
(43FH)
Pulse Train Input Minimum
Frequency
Sets the minimum frequency for the pulse train input to be detected. Enabled when H6-01 = 0,
1, or 2.
Default: 0.5 Hz
Min: 0.1 Hz
Max: 1000.0 Hz
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes