3.2 Standard Connection Diagram
3
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
71
◆
CIMR-UA2
0028 to 2
0248, 4
0011 to 4
0590
CIMR-UD2
0028 to 2
0248, 4
0011 to 4
0590
CIMR-UT2
0028 to 2
0248, 4
0011 to 4
0590
Figure 3.1
Figure 3.1 Drive Standard Connection Diagram (example: CIMR-UA2
0028/UD2
0028/UT2
0028)
<1> Note that if the drive is set to trigger a fault output whenever the fault restart function is activated (L5-02 = 1), then a sequence to interrupt
power when a fault occurs will result in shutting off the power to the drive as the drive attempts to restart itself. The default setting for L5-02
is 0 (fault output not active during restart attempt).
<2> Self-cooling motors do not require wiring that would be necessary with motors using a cooling fan.
<3> Use a three-phase power supply with a voltage of 380 to 480 V for drive models 4
0011 to 4
0414 (built-in EMC filter) and 4
0477 to
4
0590 (with stand-alone EMC filter).
+
−
+
+
+
−
+
−
ON
OFF
<5>
A+
A
B
Z
B+
Z+
AO
IG
BO
IG
ZO
IG
FE
IP
IG
TB1
SD
TB2
B track monitor
A track monitor
M
U/T
1
V/T
2
W/T
U
V
W
3
Ground
PG
+
−
+
+
+
−
+
−
S
1
S
2
S
3
S
4
S
5
S
6
S
7
MP
DM
DM
RP
A
1
A
2
A
3
0 V
AC
R
R
S
S
IG
H
1
H
2
HC
Drive
p1
n1
2 k
Ω
S
8
SC
FM
AM
0 V
0 V
AC
FM
AM
AC
E (G)
S
1
S
2
<12>
<8>
<14>
<11>
<11>
<9>
<10>
<8>
<6>
<4>
V
I
+
24 V
+
V
MA
M
1
M
2
P
1
P
2
MB
MC
PC
CN5-C
CN5-B
CN5-A
Forward Run / Stop
Reverse Run / Stop
External fault
Fault reset
Multi-speed step 1
Multi-speed step 2
External Baseblock
Jog speed
Multi-function
digital inputs
(default setting)
Sink / Source mode
selection jumper S3
(default: Sink)
Option board
connectors
Pulse Train Input (max 32 kHz)
Shield ground terminal
Multi-function
analog/ pulse
train inputs
Power 10.5 Vdc, max. 20 mA
Analog Input 1
(Frequency Reference Bias)
0 to +10 Vdc (20 k
Ω
)
Analog Input 2
(Frequency Reference Bias)
0 to +10 Vdc (20 k
Ω
)
4 to 20 mA / 0 to 20 mA (250
Ω
)
Analog Input 3
(Aux. frequency reference)
0 to +10 Vdc (20 k
Ω
)
−
V
Power supply, -10.5 Vdc, max. 20 mA
Safety
Switch
MEMOBUS/Modbus
comm. RS-422/RS-485
max. 115.2 kbps
Safe Disable inputs
Wire
jumper
Open
Safety relay /
controller
Termination resistor
(120
Ω
, 1/2 W)
DIP
Switch S2
DIP Switch S1
Fault relay output
<7>
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function relay output
(During Run)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)
Multi-function photo coupler output 1
(Zero Speed)
48 Vdc, max 50 mA
Multi-function photo coupler output 2
(Speed Agree 1)
48 Vdc, max 50 mA
Multi-function pulse train output
(Output frequency)
0 to 32 kHz (2.2 k
Ω
)
Multi-function analog output 1
(Output frequency)
-10 to +10 Vdc (2mA)
Multi-function analog output 2
(Output current)
-10 to +10 Vdc (2mA)
EDM
(Safety Electronic Device Monitor)
Main Circuit
Control Circuit
shielded line
twisted-pair shielded line
main circuit terminal
control circuit terminal
PG
B3
<2>
Cooling fan
M
FU
FV
FW
R/L1
S/L2
T/L3
MC
2MCCB
MB
ON
OFF
THRX
SA
1
2
TRX
MC MA
TRX
Fault relay
contact
Braking resistor unit
Thermal relay trip contact
MC
MC
SA
SA
THRX
ELCB (MCCB)
R
T
S
Three-phase
power supply
200 to 240
V
380 to 500 V
50
/
60
Hz
<1>
2MCCB
r1
s1
t1
MC
Wiring sequence should shut off
power to the drive when a fault
output is triggered.
If running from a 400 V power supply,
a step-down transformer is needed to
reduce the voltage to 200 V.
EMC filter
Switch
<13>
Terminals p1, n1 are for connection
options. Never connect power supply
lines to these terminals.
0 V
24 V
24
0
FE
24 V Control Power Supply
Unit Terminals
<15>
<3>