![YASKAWA U1000 Series Technical Manual Download Page 539](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114539.webp)
B.6 Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01)
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
539
Par
ame
te
r Li
s
t
B
No.
Name
Unit
Default Settings
Model CIMR-U
–
2
0192
2
0248
C6-01
Drive Duty Selection
–
HD
ND
HD
ND
0
1
0
1
o2-04
Drive Model Selection
Hex.
74
75
E2-11 (E4-11)
Motor rated Output
kW
45
55
55
75
b3-04
V/f Gain during Speed Search
%
80
80
80
80
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
b8-03
Energy Saving Control Filter Time Constant
s
0.50
2.00
2.00
2.00
b8-04
Energy Saving Coefficient Value
–
35.78
31.35
31.35
23.1
C5-17 (C5-37)
Motor Inertia
kgm
2
0.333
0.490
0.490
0.900
C6-02
Carrier Frequency Selection
–
1
1
1
1
E2-01 (E4-01)
Motor Rated Current
A
160
190
190
260
E2-02 (E4-02)
Motor Rated Slip
Hz
1.6
1.43
1.43
1.39
E2-03 (E4-03)
Motor No-Load Current
A
44
45.6
45.6
72
E2-05 (E4-05)
Motor Line to Line Resistance
Ω
0.03
0.022
0.022
0.023
E2-06 (E4-06)
Motor Leakage Inductance
%
20.2
20.5
20.5
20
E2-10 (E4-10)
Motor Iron Loss for Torque Compensation
W
852
960
960
1200
E5-01
Motor Code Selection (for PM Motors)
Hex.
1214
1214
1215
1215
L2-02
Momentary Power Loss Ride-Thru Time
s
1.2
1.3
1.3
1.5
L2-03
Momentary Power Loss Minimum Baseblock Time
s
1
1
1
1
L2-04
Momentary Power Loss Voltage Recovery Time
V
150
150
150
150
L8-02
Overheat Alarm Level
°
C
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
n5-02
Motor Acceleration Time
s
0.387
0.317
0.317
0.533
SIEP_C710636_02B_1_0.book 539 ページ 2015年11月25日 水曜日 午後4時56分