7.3 Periodic Maintenance
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
397
Pe
ri
odi
c
In
s
p
ec
ti
on
&
Mainten
ance
7
■
Alarm Outputs for Maintenance Monitors
An output can be set up to inform the user when a specific components has neared its expected performance life.
When one of multi-function digital output terminals has been assigned the maintenance monitor function (H2-
= 2F),
the terminal will close when the cooling fan, DC bus capacitors, or DC bus pre-charge relay reach 90% of the expected
performance life. Additionally the digital operator will display an alarm like shown in
to indicate the specific
components that may need maintenance.
Table 7.5 Maintenance Alarms
■
Related Drive Parameters
Parameters o4-03, o4-05, and o4-07 can be used to reset a Maintenance Monitor back to zero after a specific component
has been replaced.
Refer to Parameter Table on page 468
for details on parameter settings.
NOTICE:
If these parameters are not reset after the corresponding parts have been replaced, the Maintenance Monitor function will
continue to count down the performance life from the value that was reached with the old part. If the Maintenance Monitor is not reset,
the drive will not have the correct value of the performance life for the new component.
Alarm Display
Function
Corrective Action
LCD Operator
LT-1
<1> This alarm message will be output only if the Maintenance Monitor function is assigned to one of the digital outputs (H2-
= 2F). The alarm
will also trigger a digital output that is programmed for alarm indication (H2-
= 10).
The cooling fans have reached 90% of their designated life time.
Replace the cooling fan.
LT-2
The DC bus capacitors have reached 90% of their designated life
time.
Contact a Yaskawa representative or the nearest Yaskawa sales
office on possible drive replacement.
LT-3
The capacitor for controller has reached 90% of its designated life
time.
Contact a Yaskawa representative or the nearest Yaskawa sales
office on possible drive replacement.