C.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
579
ME
MOBUS/
M
od
bus
Co
mmuni
ca
ti
o
ns
C
◆
Broadcast Messages
Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
00E1H
oFC0
Contents (CN5-C)
bit 0
Option compatibility error (oFC00)
bit 1
Option not properly connected (oFC01)
bit 2
Same type of option card already connected (oFC02)
bit 3, 4
Reserved
bit 5
A/D Conversion Fault (oFC05)
bit 6
Option Response Error (oFC06)
bit 7 to F
Reserved
00E2H
oFC1
Contents (CN5-C)
bit 0
Option RAM Fault (oFC10)
bit 1
Option Operation Mode Fault (SLMOD) (oFC11)
bit 2
Unit Receive CRC Error (oFC12)
bit 3
Unit Receive Frame Error (oFC13)
bit 4
Unit Receive Abort Error (oFC14)
bit 5
Option Receive CRC Error (oFC15)
bit 6
Option Receive Frame Error (oFC16)
bit 7
Option Receive Abort Error (oFC17)
bit 8 to F
Reserved
00E3H
Reserved
00E4H
oFC5
Contents (CN5-C)
bit 0
Encoder Option AD Conversion Error (oFC50)
bit 1
Encoder Option Analog Circuit Error (oFC51)
bit 2
Encoder Communication Timeout (oFC52)
bit 3
Encoder Communication Data Error (oFC53)
bit 4
Encoder Error (oFC54)
bit 5
Resolver Error (oFC55)
bit 6 to F
Reserved
00E5H to 00E9H
Reserved
00EAH
Fault contents 11
bit 0 to 6
Reserved
bit 7
Damping Resistor Overheat (doH)
bit 8
Snubber Discharge Resistor Overheat (SoH)
bit 9
Internal Resistance Fault (Srr)
bit A to D
Reserved
bit E
Safety Circuit Fault (SCF)
bit F
Reserved
00EBH to 00FAH
Reserved
00FBH
Output Current
<1> Units are determined by parameter o1-03.
<2> Display is in the following units:
CIMR-U
2
0028, 2
0042, and 4
0011 to 4
0027: 0.01 A units
CIMR-U
2
0054 to 2
0248, and 4
0034 to 4
0720: 0.1 A units
CIMR-U
4
0900, 4
0930: 1 A units
<3> The contents of a communication error are saved until the fault is reset.
<4> Depending on the motor used, the correct motor pole number must be set to parameter E2-04, E4-04, or E5-04.
Register No.
Contents
0001H
Digital Input Command
bit 0
Forward Run (0: Stop 1: Run)
bit 1
Direction Command (0: Forward, 1: Reverse)
bit 2, 3
Reserved
bit 4
External Fault
bit 5
Fault Reset
bit 6 to B
Reserved
bit C
Multi-Function Digital Input S5
bit D
Multi-Function Digital Input S6
bit E
Multi-Function Digital Input S7
bit F
Multi-Function Digital Input S8
0002H
Frequency Reference
30000/100%
Register No.
Contents
SIEP_C710636_02B_1_0.book 579 ページ 2015年11月25日 水曜日 午後4時56分