6.6 Operator Programming Errors
374
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
Digital Operator Display
Error Name
oPE05
Run Command/Frequency Reference Source Selection Error
Cause
Possible Solutions
Frequency reference is assigned to an option card (b1-01 = 3) but an input option card is not
connected to the drive.
Reconnect the input option card to the drive.
The Run command is assigned to an option card (b1-02 = 3) but an input option card is not
connected to the drive.
Frequency reference is assigned to the pulse train input (b1-01 = 4), but terminal RP is not set
for frequency reference input (H6-01 > 0)
Set H6-01 to “0”.
Although the digital card input is set for BCD special for a 5 digit input (F3-01 = 6), the data
length is set for 8 bit or 12 bit (F3-03 = 0, 1).
Set the input data for 16 bit (F3-03 = 2).
The following values have been set while an AI-A3 option card is installed:
• The source of frequency reference setting is assigned to an option card (b1-01 = 3).
• The action for the analog card is set for separate terminal input (F2-01 = 0).
Make sure parameters are set properly.
Digital Operator Display
Error Name
oPE06
Control Method Selection Error
Correct the setting for the control method.
Cause
Possible Solutions
A control mode has been selected that requires a PG option card to be installed, but no PG
encoder is installed (A1-02 = 1, 3, or 7).
• Connect a PG option card.
• Correct the value set to A1-02.
Digital Operator Display
Error Name
oPE07
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02, H3-10, or H3-06
and PID functions conflict.
Cause
Possible Solutions
At least two analog input terminals are set to the same function (i.e., at least two of these
parameters has the same setting: H3-02, H3-10, or H3-06).
Change the settings to H3-02, H3-10, or H3-06 so that functions no longer conflict.
Note:
Both 0 (frequency reference bias) and F (not used) or 1F (Through mode) can be set to
H3-02, H3-10, or H3-06 at the same time.
The following simultaneous contradictory settings:
• H3-02, H3-10, or H3-06 = B (PID Feedback) while H6-01 (Pulse Train Input Terminal RP
Function Selection) = 1 (PID Feedback)
• H3-02, H3-10, or H3-06 = C (PID Setpoint Value) while H6-01 = 2 (PID Setpoint Value)
• H3-02, H3-10, or H3-06 = C (PID Setpoint Value) while b5-18 = 1 (enables b5-19 as the
PID Setpoint Value)
• H6-01 = 2 (PID Setpoint Value) while b5-18 = 1 (enables b5-19 as the PID Setpoint Value)
Disable one of the PID selections.
Digital Operator Display
Error Name
oPE08
Parameter Selection Error
A function has been set that cannot be used in the motor control method selected.
Cause
Possible Solutions
Attempted to use a function that is not valid for the selected control mode.
Check the motor control method and the functions available.
In OLV/PM, parameters E5-02 to E5-07 are set to 0.
• Set the correct motor code in accordance with the motor being used (E5-01).
• When using a special-purpose motor, set E5-
in accordance with the test report
provided.
Both E5-09 and E5-24 are set to 0, or are not 0 in control modes for PM.
Set E5-09 or E5-24 to the correct value, and set the other to “0”.
Note:
Use U1-18 to find which parameters are set outside the specified setting range. Other errors are given precedence over oPE08 when multiple errors occur at the same time.
Digital Operator Display
Error Name
oPE09
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1
to 4).
Cause
Possible Solutions
The following simultaneous contradictory settings have occurred:
• b5-15 not 0.0 (PID Sleep Function Operation Level)
• The stopping method is set to either DC Injection Braking or coast to stop with a timer
(b1-03 = 2 or 3).
• Set b5-15 to another value besides 0.
• Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
PID control is set to b5-01 = 1 or 2, but the lower limit for the frequency reference (d2-02) is
not set to 0 while reverse output is enabled (b5-11 = 1).
Correct the parameter settings.
PID control is set to b5-01 = 3 or 4, but the lower limit for the frequency reference (d2-01) is
not 0.
Correct the parameter settings.
Digital Operator Display
Error Name
oPE10
V/f Data Setting Error
The following setting errors have occurred where:
• E1-09
≤
E1-07
<
E1-06
≤
E1-11
≤
E1-04
• E3-09
≤
E3-07
<
E3-06
≤
E3-11
≤
E3-04
Cause
Possible Solutions
V/f Pattern Setting Error
Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11 (for motor 2, correct E3-04,
E3-06, E3-07, E3-09, and E3-11).
Digital Operator Display
Error Name
oPE11
Carrier Frequency Setting Error
Correct the setting for the carrier frequency.
Cause
Possible Solutions
The following simultaneous contradictory settings: C6-05 is greater than 6 and C6-04 is
greater than C6-03 (carrier frequency lower limit is greater than the upper limit). If C6-05 is
less than or equal to 6, the drive operates at C6-03.
Correct the parameter settings.
Upper and lower limits between C6-02 and C6-05 contradict each other.
SIEP_C710636_02B_1_0.book 374 ページ 2015年11月25日 水曜日 午後4時56分