5.5 E: Motor Parameters
252
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
■
E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 as shown in
Note:
Certain E3-
parameters might not be visible depending on the control mode.
Refer to Parameter Table on page 468
Figure 5.54
Figure 5.54 V/f Pattern for Motor 2
Note: 1.
The following conditions must be true when setting up the V/f pattern: E3-09
≤
E3-07
<
E3-06
≤
E3-11
≤
E3-04
2.
To make the V/f pattern a straight line at a frequency lower than E3-06, set E3-09 = E3-07. With this setting, E3-08 is disregarded.
3.
Parameters E3-04 through E3-13 are reset to their default values when the drive is initialized.
4.
E3-11, E3-12, and E3-13 rarely need to be changed, and should only be used to fine-tune the V/f pattern in the constant output range.
◆
E4: Motor 2 Parameters
E4 parameters contain the motor data for motor 2. These parameters are usually set automatically during the
Auto-Tuning process (Rotational Auto-Tuning, Stationary Auto-Tuning 2 and 3). If Auto-Tuning cannot be performed,
refer to
Auto-Tuning Fault Detection on page 376
for detail.
Note:
As the function for switching between two motors cannot be used with a PM motor, the E5-
parameters will be hidden when
a PM motor control mode is selected (A1-02 = 5, 6, or 7).
■
E4-01: Motor 2 Rated Current
Set E4-01 to the full load amps (FLA) stamped on the nameplate of motor 2. This value is used for motor protection and
to calculate torque limits. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved
to E4-01.
Note: 1.
Display is in the following units.
CIMR-U
2
0028, 2
0042, and 4
0011 to 4
0027: 0.01 A units
CIMR-U
2
0054 to 2
0248, and 4
0034 to 4
0930: 0.1 A units
2.
If the motor rated current in E4-01 is set lower than the motor no-load current in E4-03, then a parameter setting error will occur
(oPE02). E4-03 must be set correctly to prevent this error.
No.
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<2> Default setting is determined by the control mode selected for motor 2 (E3-01).
<3> The drive sets this value when Auto-Tuning is performed (Rotational Auto-Tuning and Stationary Auto-Tuning 2).
<4> Parameter ignored when E3-11 and E3-12 are set to 0.0.
<5> The default value shown here is for the following localized drives: Japan (Model code: CIMR-UA
), India (Model code: CIMR-UD
), Asia
(Model code: CIMR-UT
).
For default value of China localized drive (Model code: CIMR-UB
), refer to
Default Values of the China Localized Drive: CIMR-UB
.
Parameter Name
Setting Range
Default
E3-04
Motor 2 Max Output Frequency
40.0 to 400.0 Hz
E3-05
Motor 2 Max Voltage
0.0 to 255.0 V
E3-06
Motor 2 Base Frequency
0.0 to [E3-04]
E3-07
Motor 2 Mid Output Frequency
0.0 to [E3-04]
E3-08
Motor 2 Mid Output Frequency Voltage
0.0 to 255.0 V
E3-09
Motor 2 Minimum Output Frequency
0.0 to [E3-04]
E3-10
Motor 2 Minimum Output Frequency Voltage
0.0 to 255.0 V
E3-11
Motor 2 Mid Output Frequency 2
0.0 to [E3-04]
E3-12
Motor 2 Mid Output Frequency Voltage 2
0.0 to 255.0 V
0.0 V
E3-13
Motor 2 Base Voltage
0.0 to 255.0 V
0.0 V
No.
Parameter Name
Setting Range
Default
E4-01
Motor 2 Rated Current
10 to 150% of the drive rated current.
Determined by C6-01 and
o2-04
Output (V)
Frequency (Hz)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09
E3-07
E3-06 E3-11 E3-04