3.10 Control I/O Connections
116
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
◆
Terminal A3 Analog/PTC Input Selection (CIMR-UB
)
Terminal A3 can be configured either as multi-function analog input or as PTC input for motor thermal overload
protection. Use switch S4 to select the input function as described in
.
Figure 3.60
Figure 3.60 DIP Switch S4 (CIMR-UB
)
Table 3.23 DIP Switch S4 Settings (CIMR-UB
)
◆
Terminal AM/FM Signal Selection (CIMR-UB
)
The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal
board as explained in
. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set
accordingly. The default selection is voltage output for both terminals.
Figure 3.61
Figure 3.61 Jumper S5 (CIMR-UB
)
Table 3.24 Jumper S5 Settings (CIMR-UB
)
Table 3.25 Parameter H4-07, H4-08 Details (CIMR-UB
)
Setting
Description
AI (lower position) (default)
Analog input for the function selected in parameter H3-06
PTC (upper position)
PTC input. Parameter H3-06 must be set to E (PTC input)
Voltage Output
Current Output
Terminal AM
Terminal FM
No.
Parameter Name
Description
Setting
Range
Default
Setting
H4-07
Terminal AM signal level selection
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
0 to 2
0
H4-08
Terminal FM signal level selection
M1 M2 M5
M3 M6 M4
E(G) HC H1 H2 DM+ DM- IG R+ R- S+ S-
V+ AC V- A1 A2 A3 FM AM AC MP RP AC
PTC
AI
DIP Switch S4
Terminal A3 Analog/
PTC Input Sel.
M1 M2 M5
M3 M6 M4
E(G) HC H1 H2 DM+ DM- IG R+ R- S+ S-
V+ AC V- A1 A2 A3 FM AM AC MP RP AC
AM
FM
V
I
Jumper S5
Terminal AM/FM Signal
Selection
AM
FM
V
I
AM
FM
V
I
AM
FM
V
I
AM
FM
V
I