B.3 Parameter Table
470
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
■
b2: DC Injection Braking
■
b3: Speed Search
b1-15
(1C4H)
Frequency Reference Selection 2
Enabled when an input terminal set for “External reference” (H1-
= 2) closes.
0: Digital operator
1: Terminals (analog input terminals)
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse train input
Default: 0
Min: 0
Max: 4
b1-16
(1C5H)
Run Command Selection 2
Enabled when a terminal set for “External reference” (H1-
= 2) closes.
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option card
Default: 0
Min: 0
Max: 3
b1-17
(1C6H)
Run Command at Power Up
0: Disregarded. A new Run command needs to be issued after power up.
1: Allowed. Motor will start immediately after power up if a Run command is already enabled.
Default: 0
Min: 0
Max: 1
b1-21
(748H)
Start Condition Selection at Closed
Loop Vector Control
There is normally no need to change this parameter from the default value.
Selects a condition to start Closed Loop Vector Control.
0: Run command is not accepted when b2-01
≤
Motor speed < E1-09.
1: Run command is accepted when b2-01
≤
Motor speed < E1-09.
Default: 0
Min: 0
Max: 1
b1-24
(B2CH)
Commercial Power Operation
Switching Selection
0: Disabled
1: Enabled
Default: 0
Min: 0
Max: 1
b1-25
(B2DH)
Commercial Power Supply
Operation Cancellation Level
Set the switching level to switch to PWM switching mode in 0.1 Hz units.
Default: 1.0 Hz
Min: 0.4 Hz
Max: 6.0 Hz
b1-26
(B2EH)
Commercial Power Supply
Operation Switching Level
Set the switching level to switch to the commercial power supply operation in 0.1 Hz units.
Default: 0.2 Hz
Min: 0.0 Hz
Max: 3.0 Hz
<11> Setting range is 0, 1, or 3 when the control mode is CLV, OLV/PM, AOLV/PM, or CLV/PM.
No.(Addr.)
Name
Description
Setting
Page
b2-01
(189H)
<10> Default setting is determined by the control mode (A1-02).
DC Injection Braking Start
Frequency
Sets the frequency at which DC Injection Braking starts when “Ramp to stop” (b1-03 = 0) is
selected.
Min: 0.0 Hz
Max: 10.0 Hz
b2-02
(18AH)
DC Injection Braking Current
Sets the DC Injection Braking current as a percentage of the drive rated current.
Default: 50%
Min: 0%
Max: 100%
b2-03
(18BH)
DC Injection Braking Time at Start
Sets the time of DC Injection Braking (Zero Speed Control when in CLV and CLV/PM) time at
start. Disabled when set to 0.00 s.
Default: 0.00 s
Min: 0.00 s
Max: 10.00 s
b2-04
(18CH)
DC Injection Braking Time at Stop
Sets the time of DC Injection Braking (Zero Speed Control when in CLV and CLV/PM) at stop.
Min: 0.00 s
Max: 10.00 s
b2-08
(190H)
Magnetic Flux Compensation
Value
Sets the magnetic flux compensation as a percentage of the no-load current value (E2-03).
Default: 0%
Min: 0%
Max: 1000%
No.(Addr.)
Name
Description
Setting
Page
b3-01
(191H)
Speed Search Selection at Start
0: Disabled
1: Enabled
Min: 0
Max: 1
b3-03
(193H)
Speed Search Deceleration Time
Sets output frequency reduction time during Speed Search.
Default: 2.0 s
Min: 0.1 s
Max: 10.0 s
No.(Addr.)
Name
Description
Setting
Page
All Modes
All Modes
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
V/f w/PG
V/f
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
V/f w/PG
V/f
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
V/f w/PG
V/f
OLV
CLV/PM
CLV
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
All Modes
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV