B.3 Parameter Table
486
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
■
E3: V/f Pattern for Motor 2
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).
■
E4: Motor 2 Parameters
These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).
No.(Addr.)
Name
Description
Setting
Page
E3-01
(319H)
<18> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<24> Parameter ignored when E3-11 (Motor 2 Mid Output Frequency 2) and E3-12 (Motor 2 Mid Output Frequency Voltage 2) are set to 0.
<25> Default setting depends on the control mode for motor 2 set in parameter E3-01. The value shown here is for V/f Control.
<44> The default value shown here is for the following localized drives: Japan (Model code: CIMR-UA
), India (Model code: CIMR-UD
), Asia
(Model code: CIMR-UT
). For default value of China localized drive (Model code: CIMR-UB
<50> When E3-13 (Motor 2 Base Voltage) is set to 0.0, output voltage is controlled with E3-05 (Motor 2 Max. Voltage) = E3-13. When
Auto-Tuning is performed, E3-05 and E3-13 are automatically set to the same value.
Motor 2 Control Mode Selection
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
Default: 0
Min: 0
Max: 3
E3-04
(31AH)
Motor 2 Max. Output Frequency
To set linear V/f characteristics, set the same values for E3-07 and E3-09. In this case, the
setting for E3-08 will be disregarded. Ensure that the five frequencies are set according to these
rules or an oPE10 fault will occur:
E3-09
≤
E3-07
<
E3-06
≤ Ε3−11 ≤
E3-04
Note that if E3-11 = 0, then both E3-11 and E3-12 are disabled, and the above conditions do not
apply.
Note:
E3-07 and E3-08 are only available in the following control modes: V/f, V/f w/PG and
OLV.
Min: 40.0 Hz
Max: 400.0 Hz
E3-05
(31BH)
Motor 2 Max. Voltage
Min: 0.0 V
Max: 255.0 V
E3-06
(31CH)
Motor 2 Base Frequency
Min: 0.0 Hz
Max: E3-04
E3-07
(31DH)
Motor 2 Mid Output Frequency
Min: 0.0 Hz
Max: E3-04
E3-08
(31EH)
Motor 2 Mid Output Frequency
Voltage
Min: 0.0 V
Max: 255.0 V
E3-09
(31FH)
Motor 2 Minimum Output
Frequency
Min: 0.0 Hz
Max: E3-04
E3-10
(320H)
Motor 2 Minimum Output
Frequency Voltage
Min: 0.0 V
Max: 255.0 V
E3-11
(345H)
Motor 2 Mid Output Frequency 2
Default: 0.0 Hz
Min: 0.0 Hz
Max: E3-04
E3-12
(346H)
Motor 2 Mid Output Frequency
Voltage 2
Default: 0.0 V
Min: 0.0 V
Max: 255.0 V
E3-13
(347H)
Motor 2 Base Voltage
Default: 0.0 V
Min: 0.0 V
Max: 255.0 V
No.(Addr.)
Name
Description
Setting
Page
E4-01
(321H)
Motor 2 Rated Current
Sets the full load current for motor 2. Automatically set during Auto-Tuning.
Min: 10% of drive rated
current
Max: 150% of drive
rated current
E4-02
(322H)
Motor 2 Rated Slip
Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
Min: 0.00 Hz
Max: 20.00 Hz
E4-03
(323H)
Motor 2 No-Load Current
Sets the no-load current for motor 2. Automatically set during Auto-Tuning.
Min: 0 A
Max: E4-01
E4-04
(324H)
Motor 2 Motor Poles
Sets the number of poles of motor 2. Automatically set during Auto-Tuning.
Default: 4
Min: 2
Max: 48
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
Output Voltage (V)
Frequency (Hz)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09
E3-07 E3-06 E3-11 E3-04
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV