![YASKAWA U1000 Series Technical Manual Download Page 294](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114294.webp)
5.7 H: Terminal Functions
294
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
Figure 5.86
Figure 5.86 Speed Control with ASR in V/f with Simple Speed Feedback
Enabling V/f Control with Simple Speed Feedback:
1.
Set the drive to V/f Control (A1-02 = 0).
2.
Connect the motor speed pulse signal to the pulse input RP, set H6-01 = 3, and set the pulse signal frequency
that is equal to the maximum speed to H6-02 (pulse train input scaling). Make sure the pulse input bias (H6-04)
is 0% and the gain (H6-03) is 100%.
3.
Decide the signal used for detecting the direction. If a digital input is used, set H1-
= 7E.
4.
Use the ASR gain and integral time parameters described in
C5: Automatic Speed Regulator (ASR) on
for adjusting the responsiveness.
Note: 1.
C5 parameters will appear when using V/f Control (A1-02 = 0) and when the pulse input RP function is set for simple PG feedback in
V/f Control (H6-01 = 3).
2.
If running two motors from the same drive, note that the V/f Control with simple PG feedback can be used for motor 1 only.
■
H6-02: Pulse Train Input Scaling
This parameter sets the pulse signal frequency that is equal to 100% of the input value selected in parameter H6-01.
■
H6-03: Pulse Train Input Gain
Sets the level of the input value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to
terminal RP.
■
H6-04: Pulse Train Input Bias
Sets the level of the input value selected in H6-01 when no signal (0 Hz) is input to terminal RP.
■
H6-05: Pulse Train Input Filter Time
Sets the pulse train input filter time constant in seconds.
No.
Name
Setting Range
Default
H6-02
Pulse Train Input Scaling
100 to 32000 Hz
1440 Hz
No.
Name
Setting Range
Default
H6-03
Pulse Train Input Gain
0.0 to 1000.0%
100.0%
No.
Name
Setting Range
Default
H6-04
Pulse Train Input Bias
-100.0 to 100.0%
0.0%
No.
Name
Setting Range
Default
H6-05
Pulse Train Input Filter Time
0.00 to 2.00 s
0.10 s
Motor speed
Output Frequency
after Soft Starter
SIEP_C710636_02B_1_0.book 294 ページ 2015年11月25日 水曜日 午後4時56分