5.7 H: Terminal Functions
272
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
Setting 1A: Accel/decel time selection 2
Used to select accel/decel times 1 to 4 in combination with the Accel/decel time selection 1 command.
C1-08: Accel, Decel Times 1 to 4 on page 216
for details.
Setting 1B: Program lockout
When an input is programmed for Program Lockout, parameters values cannot be changed as long as this input is open (it
is still possible to view and monitor parameter settings).
Setting 1E: Reference sample hold
This function allows the user to sample an analog frequency reference signal being input to terminal A1, A2, or A3 and
hold the frequency reference at the sampled level. Once the Analog Frequency Reference Sample/Hold function is held
for at least 100 ms, the drive reads the analog input and changes the frequency reference to the newly sampled speed as
illustrated in
.
When the power is shut off and the sampled analog frequency reference is cleared, the frequency reference is reset to 0.
Figure 5.63
Figure 5.63 Analog Frequency Reference Sample/Hold
An oPE03 error will occur when one of the following functions is used simultaneously with the Analog frequency
reference sample/hold command.
• Accel/decel ramp hold (setting: A)
• Up command, Down command (setting: 10, 11)
• Offset frequency (setting: 44 to 46)
• Up or Down 2 command (setting: 75, 76)
Setting 20 to 2F: External fault
By using the External fault command, the drive can be stopped when problems occur with external devices.
To use the External fault command, set one of the multi-function digital inputs to any value between 20 to 2F. The digital
operator will display EF
where
is the number of the terminal to which the external fault signal is assigned.
For example, if an external fault signal is input to terminal S3, “EF3” will be displayed.
Select the value to be set in H1-
from a combination of any of the following three conditions:
• Signal input level from peripheral devices (N.O., N.C.)
• External fault detection method
• Operation after external fault detection
shows the relationship between the conditions and the value set to H1-
:
Table 5.38 Stopping Method for External Fault
Setting
Terminal Status
Detection Conditions
Stopping Method
N.O.
N.C.
Always Detected
Detected during
Run only
Ramp to Stop
(fault)
Coast to Stop
(fault)
Fast Stop
(fault)
Alarm Only
(continue running)
20
–
–
–
–
–
21
–
–
–
–
–
22
–
–
–
–
–
23
–
–
–
–
–
24
–
–
–
–
–
25
–
–
–
–
–
26
–
–
–
–
–
27
–
–
–
–
–
28
–
–
–
–
–
Frequency
reference
Time
100 ms
Reference
Sample Hold Input
Analog signal
100 ms
ON
OFF