Setting Value
Function
Description
Ref.
160
!Internal Cooling Fan
Failure
The terminal deactivates when the drive detects a cooling fan failure in the drive.
161
!Pole Position Detection
Complete
The terminal deactivates when drive receives a Run command and the drive detects the motor magnetic pole position
of the PM motor.
162
!Modbus Reg 1 Status
Satisfied
The terminal deactivates when the bit specified by
H2-08 [Modbus Register 1 Bit Select]
for the MEMOBUS register
address set with
H2-07 [Modbus Register 1 Address Select]
activates.
163
!Modbus Reg 2 Status
Satisfied
The terminal deactivates when the bit specified by
H2-10 [Modbus Register 2 Bit Select]
for the MEMOBUS register
address set with
H2-09 [Modbus Register 2 Address Select]
activates.
169
!External Power 24V
Supply
The terminal deactivates when there is an external 24V power supply between terminals PS-AC.
ON : An external 24V power supply does not supply power.
OFF : An external 24V power supply supplies power.
16A
!Data Logger Error
The terminal deactivates when the drive detects
LoG [Com Error / Abnormal SD card]
.
171
!Low PI2 Control
Feedback Level
The terminal deactivates when the PI2 Control Feedback Level is less than
S3-13 [PI2 Control Low Feedback Lvl]
.
172
!High PI2 Control
Feedback Level
The terminal deactivates when the PI2 Control Feedback Level is more than
S3-15 [PI2 Control High Feedback Lvl]
.
189
!Output Current Lim
The terminal deactivates when the output current limit is limiting the drive output speed.
190
!DWEZ Digital Outputs 1
Sets the digital output 1 to use in DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
191
!DWEZ Digital Outputs 2
Sets the digital output 2 to use in DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
192
!DWEZ Digital Outputs 3
Sets the digital output 3 to use in DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
194
!Loss of Prime
The terminal deactivates when the drive is in an
LOP [Loss of Prime]
condition.
195
!Thermostat Fault
The terminal deactivates when the terminal set for
H1-xx = 88 [MFDI Function Selection = Thermostat Fault]
is
active.
196
!High Feedback
The terminal deactivates when the drive is in a High Feedback Condition as specified by
Y1-11 [High Feedback Level]
and
Y1-12 [High Feedback Lvl Fault Dly Time]
and when the drive detects an
HFB [High Feedback Sensed]
fault or
an
HIFB [High Feedback Sensed]
alarm.
197
!Low Feedback
The terminal deactivates when the drive is in a Low Feedback Condition as specified by
Y1-08 [Low Feedback Level]
and
Y1-09 [Low Feedback Lvl Fault Dly Time]
and when the drive detects an
LFB [Low Feedback Sensed]
fault or an
LOFB [High Feedback Sensed]
alarm.
19E
!Low PI Auxiliary
Control Level
The terminal deactivates when the PI Aux Feedback Level is less than
YF-09 [PI Aux Control Low Level Detect]
or if
the drive detects an
LOAUX [Low PI Aux Feedback Level]
fault.
19F
!High PI Auxiliary
Control Level
The terminal deactivates when the PI Aux Feedback Level is more than
YF-12 [PI Aux Control High Level Detect]
or
if the drive detects an
HIAUX [High PI Aux Feedback Level]
fault.
1A9
!RELAY Operator
Control
The terminal changes to OFF or ON when you push the RELAY (
) button. When the terminal is ON, push
to turn it OFF. When the terminal is OFF, push
to turn in ON.
1AA
!Utility Delay
The terminal deactivates when the drive is stopped and is waiting for the timer set in
Y4-17 [Utility Start Delay]
to
expire.
1AB
!Thrust Mode
The terminal deactivates when the output frequency is between 0.0 Hz and the value set in
Y4-12 [Thrust Frequency]
and the Thrust Bearing function is active.
1AC
!Setpoint Not Maintained
The terminal deactivates when the drive detects
NMS [Setpoint Not Met]
condition.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV