52
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H1-67
(39E7)
RUN
Terminal S7 On-Delay
Time
Sets the length of time necessary for Terminal S7 to be closed before the drive does the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-71
(39EB)
RUN
Terminal S1 Off-Delay
Time
Sets the length of time necessary for Terminal S1 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-72
(39EC)
RUN
Terminal S2 Off-Delay
Time
Sets the length of time necessary for Terminal S2 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-73
(39ED)
RUN
Terminal S3 Off-Delay
Time
Sets the length of time necessary for Terminal S3 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-74
(39EE)
RUN
Terminal S4 Off-Delay
Time
Sets the length of time necessary for Terminal S4 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-75
(39EF)
RUN
Terminal S5 Off-Delay
Time
Sets the length of time necessary for Terminal S5 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-76
(39F0)
RUN
Terminal S6 Off-Delay
Time
Sets the length of time necessary for Terminal S6 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
H1-77
(39F1)
RUN
Terminal S7 Off-Delay
Time
Sets the length of time necessary for Terminal S7 to be open before the drive removes the
programmed function.
0.00 s
(0.00 - 300.00 s)
■
H1-xx: MFDI Setting Values
Setting Value
Function
Description
Ref.
0
3-Wire Sequence
Sets the direction of motor rotation for 3-wire sequence.
3
Multi-Step Speed
Reference 1
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
4
Multi-Step Speed
Reference 2
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
5
Multi-Step Speed
Reference 3
Uses speed references
d1-01 to d1-08
to set a multi-step speed reference.
6
Jog Reference Selection
Sets the drive to use the JOG Frequency Reference (JOG command) set in
d1-17 [Jog Reference]
. The JOG Frequency
Reference (JOG command) overrides the
d1-01 to d1-08 [References 1 to 8]
settings.
7
Accel/Decel Time
Selection 1
Sets the drive to use
Acceleration/Deceleration Time 1 [C1-01, C1-02]
or
Acceleration/Deceleration Time 2 [C1-03,
C1-04]
.
8
Baseblock Command (N.
O.)
Sets the command that stops drive output and coasts the motor to stop when the input is ON.
ON : Baseblock (drive output stop)
OFF : Normal operation
9
Baseblock Command (N.
C.)
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
ON : Normal operation
OFF : Baseblock (drive output stop)
A
Accel/Decel Ramp Hold
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency
that was stored in the drive at the time of the pause, and restarts motor operation.
B
Overheat Alarm (oH2)
Sets the drive to display an
oH2 [Drive Overheat Warning]
alarm when the input terminal is ON. The alarm does not
have an effect on drive operation.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV