318
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
Note:
The terminal deactivates in these conditions:
•
During Stop
•
During baseblock
•
During DC Injection Braking (initial excitation)
•
During Short Circuit Braking
Figure 2.70 Active Frequency Output Time Chart
■
38: Drive Enabled
Setting Value
Function
Description
38
Drive Enabled
This terminal activates when the
H1-xx = 6A [Drive Enable]
terminal activates.
■
39: Watt Hour Pulse Output
Setting Value
Function
Description
39
Watt Hour Pulse Output
Outputs the pulse that shows the watt hours.
Note:
Refer to
“
H2-06: Watt Hour Output Unit Selection
”
for more information.
■
3A: Drive Overheat Alarm
Setting Value
Function
Description
3A
Drive Overheat Alarm
The terminal activates when the drive heatsink temperature is at the
L8-02 [Overheat Alarm Level]
setting while
L8-03 = 4
[Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)]
and the drive is running.
The drive will decrease the frequency reference as specified by
L8-19 [Freq Reduction @ oH Pre-Alarm]
. Carrier
frequency reduction is active when
L8-97 = 1 [Carrier Freq Reduce during OH = Enabled]
.
■
3D: During Speed Search
Setting Value
Function
Description
3D
During Speed Search
The terminal activates when the drive is doing speed search.
Note:
Refer to
“
b3: Speed Search
”
for more information.
■
42: Pressure Reached
Setting Value
Function
Description
42
Pressure Reached
The terminal activates when the drive is at the Pressure Setpoint.
The drive uses the Pressure Feedback and
Y4-36 [Pressure Reached Exit Conditions]
to
Y4-40 [Pressure Reached
Detection Sel]
for the activation and deactivation conditions.
When the
b5-09 [PID Output Level Selection]
setting changes, the MFDO terminal operation also changes.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV