434
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
shows an example of sequence timer operation when you set the drive parameters as specified in
Table 2.70 Parameter Settings for Example of Sequence Timer 3
Tine Display Format
Sequence Timer 1
Sequence Timer 2
Sequence Timer 3
Sequence Timer 4
o4-22 = 0
[24 Hour Clock]
S2-01 = 05:00
S2-06 = 15:00
S2-11 = 09:00
-
S2-02 = 15:00
S2-07 = 22:00
S2-12 = 24:00
-
S2-03 = 2
[Mon - Fri]
S2-08 = 2
[Mon - Fri]
S2-13 = 9
[Saturday]
S2-18 = 0
[Timer Disabled]
S2-04 = 1
[Run]
S2-09 = 2
[Run - PI Disable]
S2-14 = 1
[Run]
-
S2-05 = 0
[Operator (d1-01/YA-01)]
S2-10 = 1
[Operator (d1-02/YA-02)]
S2-15 = 2
[Operator (d1-03/YA-03)]
-
d1-01:
d1-02:
d1-03:
Figure 2.113 Example of Sequence Timer 3
■
Sequence Timer Home Screen Text
When you set
o1-40 = 0 [Home Screen Display Selection = Custom Monitor]
, the message text on the Status Monitor
will show the status of the Sequence Timer when the Sequence Timer has an effect on the drive Run condition.
•
When you set the Sequence Timers to use for Digital Output only (
S2-04 [Timer 1 Sequence Selection]
,
S2-09
[Timer 2 Sequence Selection]
,
S2-14 [Timer 3 Sequence Selection]
, and
S2-19 [Timer 4 Reference Source] = 0
[Digital Out Only]
), the message text will not show the status of the Sequence Timer.
•
When the drive uses the Sequence Timers to overwrite the Run command in AUTO (
S2-04
,
S2-09
,
S2-14
, or
S2-19
≠ 0
), the drive will update the message text. Refer to
for more information.