YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
473
Delta to Setpoint Entry for Sleep Wake-up Level
Delta to Setpoint Entry lets you set
Y1-04 [Sleep Wake-up Level]
relative to the current setpoint and set a PID setpoint
when PID is not active.
Parameter/Condition
Delta Entry
Absolute Entry
Y1-04
b5-09 = 0 [PID Output Level Selection = Normal Output (Direct Acting)]
-0.00 to -99.99
0.00 to 99.99
Y1-04
b5-09 = 1 [Reverse Output (Reverse Acting)]
+0.00 to +99.99
0.00 to 99.99
Table 2.80 Absolute Mode and Delta to Setpoint Mode
Entry Mode
Keypad Display
Description
Absolute
The value set for
Y1-04
represents the feedback level that will wake-up the drive. You can
set
Y1-04
as an absolute value.
Delta to Setpoint
When the left-most digit changes to a Δ (delta), you can set a Sleep Wake-up Level relative
to the setpoint.
The effective Wake-up Level changes when
b5-09
changes:
•
b5-09 = 0
:
“
Setpoint -
Y1-04
”
•
b5-09 = 1
:
“
Se
Y1-04
”
■
Y2-01: Sleep Level Type
No.
(Hex.)
Name
Description
Default
(Range)
Y2-01
(3C64)
Sleep Level Type
Sets the data source that the drive uses to know when to activate the Sleep Function.
5
(0 - 5)
0 : Output Frequency
1 : Output Current
2 : Feedback
3 : Output Speed (RPM)
5 : Output Frequency (non-PID)
Note:
•
Feedback depends on PID direction operation.
•
When the Sleep Function is active, the keypad will show the
“
Sleep
”
Alarm.
■
Y2-02: Sleep Level
No.
(Hex.)
Name
Description
Default
(Range)
Y2-02
(3C65)
RUN
Sleep Level
Sets the level that the level type set in
Y2-01 [Sleep Level Type]
must be at for the time set in
Y2-03
[Sleep Delay Time]
for the drive to enter Sleep Mode.
0.0
(0.0 - 6000.0)
When the monitor data of the level type set in
Y2-01
is less than this level for longer than the time set in
Y2-03
, the
drive will enter Sleep Mode.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV