No.
(Hex.)
Name
Description
Default
(Range)
Ref.
YF-10
(3F59)
RUN
PI Aux Low Level
Detection Time
Sets the length of time that the PI Aux Feedback must be less than
YF-09 [PI Aux Control
Low Lvl Detection]
to trigger a drive response when
YF-11 = 2 and 3 [PI Aux Control Low
Level Det Sel = Fault and Auto-Restart (time set by YF-15)]
.
0.1 s
(0.0 - 300.0 s)
YF-11
(3F5A)
PI Aux Control Low
Level Det Sel
Sets drive response when the PI Aux Feedback decreases to less than
YF-09 [PI Aux
Control Low Lvl Detection]
for longer than
YF-10 [PI Aux Control Low Lvl Det Time]
.
0 : No Display
1 : Alarm Only
2 : Fault
3 : Auto-Restart (time set by YF-15)
Note:
•
Set
YF-01 = 1 [PI Aux Control Selection = Enabled]
and
YF-09 [PI Aux Control
Low Level Detect]
> 0 to enable PI Aux Low Level Detection.
•
Parameter
YF-10
only applies when
YF-11 = 2 or 3
.
1
(0 - 3)
YF-12
(3F5B)
RUN
PI Aux Control High
Level Detect
Sets the value above which the level must be for longer than
YF-13 [PI Aux High Level
Detection Time]
to respond as specified by
YF-14 [PI Aux Hi Level Detection Select]
.
Note:
•
Set this parameter to 0.0 to disable the function.
•
Parameter
YF-13
only applies to when
YF-14 = 2 and 3 [Fault and Auto-Restart
(time set by YF-15)]
.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level
Decimal Place Pos]
set the unit and resolution.
0.0 PSI
(-999.9 - +999.9 PSI)
YF-13
(3F5C)
RUN
PI Aux High Level
Detection Time
Sets the length of time that the level must be more than
YF-12 [PI Aux Control High Level
Detect]
before the drive will respond when
YF-14 = 2, 3 [PI Aux Hi Level Detection
Select]
.
0.1 s
(0.0 - 300.0 s)
YF-14
(3F5D)
PI Aux Control Hi Level
Det Sel
Sets the drive response when the PI Aux Feedback increases to more than the
YF-12 [PI
Aux Control High Level Detect]
level for longer than the time set in
YF-13 [PI Aux High
Level Detection Time]
.
0 : NoDisplay (Digital Output Only)
1 : Alarm Only
2 : Fault
3 : Auto-Restart (time set by YF-15)
Note:
•
Set
YF-01 = 1 [PI Aux Control Selection = Enabled]
and
YF-12 [PI Aux Control
High Level Detect]
> 0 to enable PI Aux High Level Detection.
•
Parameter
YF-13
only applies when
YF-14 = 2 or 3
1
(0 - 3)
YF-15
(3F5E)
PI Aux Level Detect
Restart Time
Sets the length of time the drive will wait before it tries an Auto-Restart of
LOAUX [Low
PI Aux Feedback Level]
or
HIAUX [High PI Aux Feedback Level]
fault.
5.0 min
(0.1 - 6000.0 min)
YF-16
(3F5F)
RUN
PI Auxiliary Control P
Gain
Sets the proportional gain for the suction pressure control.
2.00
(0.00 - 25.00)
YF-17
(3F60)
RUN
PI Auxiliary Control I
Time
Sets the integral time for the suction pressure control.
Note:
Set this parameter to 0.0 to disable the integrator.
5.0 s
(0.0 - 360.0 s)
YF-18
(3F61)
PI Aux Control Detect
Time Unit
Sets the time unit for
YF-10 [PI Aux Control Low Lvl Det Time]
and
YF-13 [PI Aux High
Level Detection Time]
.
0 : Minutes (min)
1 : Seconds (sec)
1
(0, 1)
YF-19
(3F62)
PI Aux Ctrl Feedback
WireBreak
Sets how the analog input selected for PI Aux Feedback will respond when it is
programmed to receive a 4 mA to 20 mA signal and the signal is lost.
0 : Disabled
1 : Alarm Only
2 : Fault (no retry, coast to stop)
2
(0 - 2)
YF-20
(3F63)
PI Aux Main PI Speed
Control
Sets if the PI Auxiliary Controller has an effect on output speed.
0 : Disabled
1 : Enabled
1
(0, 1)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV