2.11 o: Keypad-Related Settings
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
421
Note:
The drive can write data to the keypad a maximum of 100,000 times. If you write data to the keypad more than 100,000 times, you must
replace the keypad.
0 : Every 10 minutes
1 : Every 30 minutes
2 : Every 60 minutes
3 : Every 12 hours
◆
o4: Maintenance Mon Settings
o4 parameters
set the expected service life to help you know when to replace parts. The drive will show an alarm to
tell you when the replacement part interval is near.
■
o4-01: Elapsed Operating Time Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-01
(050B)
Elapsed Operating Time
Setting
Sets the initial value of the cumulative drive operation time in 10-hour units.
0 h
(0 - 9999 h)
When you select
o4-01
on the keypad, it will show the current value of
U4-01
in units of 10 hours (h). When you
change the setting of
o4-01
through the monitor, the
U4-01
count starts again as specified by the setting of
o4-01
.
Note:
Set this parameter in 10-hour (h) units. When
o4-01 = 30
,
U4-01 [Cumulative Ope Time] = 300 h
.
■
o4-02: Elapsed Operating Time Selection
No.
(Hex.)
Name
Description
Default
(Range)
o4-02
(050C)
Elapsed Operating Time
Selection
Sets the condition that counts the cumulative operation time.
1
(0, 1)
0 : U4-01 Shows Total Power-up Time
Counts the time from when you energize drive to when you de-energize the drive.
1 : U4-01 Shows Total RUN Time
Counts the time that the drive outputs voltage.
■
o4-03: Fan Operation Time Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-03
(050E)
Fan Operation Time Setting
Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour units.
0 h
(0 - 9999 h)
Use monitor
U4-03 [Cooling Fan Ope Time]
to view the total operation time of the cooling fan. When you replace a
cooling fan, set
o4-03 = 0
to reset
U4-03
. Select
o4-03
on the keypad to show the current value of
U4-03
in 10-hour
(h) units. If you use the monitor to change
o4-03
, the recount of
U4-03
starts with the
o4-03
setting.
Note:
The drive sets
o4-03
in 10-hour (h) units. When
o4-03 = 30
,
U4-03 [Cooling Fan Ope Time]
will show
“
300 h
”
.
■
o4-05: Capacitor Maintenance Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-05
(051D)
Capacitor Maintenance
Setting
Sets the
U4-05 [CapacitorMaintenance]
monitor value.
0%
(0 - 150%)
When you replace a drive, set
o4-05 = 0
to reset
U4-05
. When the
o4-05
setting changes, the count of
U4-05
starts
again as specified by the setting of
o4-05
. After you complete the configuration,
o4-05
automatically resets to
0
.