TOEPYAIHV6002A HV600 Drive Programming
Note:
•
For settings 1 and 2, the adjustment time can cause a delay before startup.
•
For settings 1 and 2, the drive can set the line-to-line resistance value of
E9-10 [Motor Line-to-Line Resistance]
.
•
When the temperature will change at startup, use setting 2.
•
To decrease the startup time, set this parameter to 0, then do line-to-line resistance tuning.
•
If you will start from coasting, set this parameter to 0, then do line-to-line resistance tuning.
◆
n8: PM Motor Control Tuning
n8 parameters
are used to make adjustments when controlling PM motors.
■
n8-23: ACR q Gain @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-23
(0556)
Expert
ACR q Gain @PoleEst
Sets the proportional gain for current regulator q-axis control when the drive estimates the initial
pole. Usually it is not necessary to change this setting.
0
(0 - 2000)
■
n8-24: ACR q Integral Time @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-24
(0557)
Expert
ACR q Integral Time
@PoleEst
Sets the integral time for current regulator q-axis control when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
0.0 ms
(0.0 - 100.0 ms)
■
n8-25: ACR q Limit @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-25
(0558)
Expert
ACR q Limit @PoleEst
Sets the q-axis limit of the current regulator when the drive estimates the initial pole. Usually it is not
necessary to change this setting.
0%
(0 - 150%)
■
n8-26: ACR d Gain @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-26
(0559)
Expert
ACR d Gain @PoleEst
Sets the proportional gain for current regulator d-axis control when the drive estimates the initial
pole. Usually it is not necessary to change this setting.
500
(0 - 2000)
■
n8-27: ACR d Integral Time @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-27
(055A)
Expert
ACR d Integral Time
@PoleEst
Sets the integral time for current regulator d-axis control when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
0.0 ms
(0.0 - 100.0 ms)
■
n8-28: ACR d Lim @PoleEst
No.
(Hex.)
Name
Description
Default
(Range)
n8-28
(055B)
Expert
ACR d Lim @PoleEst
Sets the d-axis limit of the current regulator when the drive estimates the initial pole. Usually it is not
necessary to change this setting.
100%
(0 - 150%)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV