n8-49
(053C)
Heavy Load Id Current
Sets the d-axis current to that the drive will supply to the motor to run it at a constant speed
with a heavy load. Considers
E5-03 [PM Motor Rated Current (FLA)]
to be 100%. Usually
it is not necessary to change this setting.
Determined by E5-01
(-200.0 - +200.0%)
n8-50
(053D)
Medium Load Iq Level
(High)
Sets the load current level to start high efficiency control as a percentage of
E5-03 [PM
Motor Rated Current (FLA)]
. Usually it is not necessary to change this setting.
80%
(50 - 255%)
n8-51
(053E)
Pull-in Current @
Acceleration
Sets the pull-in current allowed to flow during acceleration/deceleration as a percentage of
the motor rated current.
Note:
Parameter
A1-02 [Control Method Selection]
selects which parameter is the motor
rated current.
•
A1-02 = 5 [OLV/PM]
:
E5-03 [Motor Rated Current (FLA)]
•
A1-02 = 8 [EZOLV]
:
E9-06 [Motor Rated Current (FLA)]
Determined by A1-02
(0 - 200%)
n8-52
(053F)
Expert
ACR P Gain
Sets the proportional gain of the current regulator. Usually it is not necessary to change this
setting.
10.0
(-100.0 - 100.0)
n8-54
(056D)
Expert
Voltage Error
Compensation Time
Sets the time constant that the drive uses when adjusting for voltage errors.
1.00 s
(0.00 - 10.00 s)
n8-55
(056E)
Motor to Load Inertia
Ratio
Sets the ratio between motor inertia and machine inertia.
0 : Below 1:10
1 : Between 1:10 and 1:30
2 : Between 1:30 and 1:50
3 : Beyond 1:50
0
(0 - 3)
n8-56
(056F)
Expert
PM High Performance
Selection
Usually it is not necessary to change this setting. Sets the high efficiency control method
for IPM motor.
0 : Disabled
1 : Enabled (Vd)
2 : Enabled (Vd & Vq)
1
(0 - 2)
n8-62
(057D)
Expert
Output Voltage Limit
Level
Sets the output voltage limit to prevent saturation of the output voltage. Usually it is not
necessary to change this parameter.
Note:
•
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this parameter is available in
Expert Mode.
•
When
A1-02 = 8
, the default setting is:
–
208 V Class: 230.0 V
–
480 V Class: 460.0 V
208 V Class: 200.0 V,
480 V Class: 400.0 V
(208 V Class: 0.0 - 240.0
V,
480 V Class: 0.0 - 480.0
V)
n8-63
(057E)
Expert
Output Voltage Limit P
Gain
Sets the proportional gain for output voltage control. Usually it is not necessary to change
this setting.
1.00
(0.00 - 100.00)
n8-64
(057F)
Expert
Output Voltage Limit I
Time
Sets the integral time for output voltage control. Usually it is not necessary to change this
setting.
0.040 s
(0.000 - 5.000)
n8-65
(065C)
Expert
Speed Fdbk Gain @ oV
Suppression
Sets the gain of internal speed feedback detection suppression while the overvoltage
suppression function is operating as a magnification value. Usually it is not necessary to
change this parameter.
1.50
(0.00 - 10.00)
n8-66
(0235)
Expert
Output Voltage Limit
Filter Time
Sets the filter time constant for output voltage control. Usually it is not necessary to change
this setting.
0.020 s
(0.000 - 5.000)
n8-74
(05C3)
Light Load Iq Level
Set
n8-48 [Pull-in/Light Load Id Current]
to the percentage of load current (q-axis current)
that you will apply, where
E5-03 [Motor Rated Current (FLA)] = a setting value of 100%
.
30%
(0 - 255%)
n8-75
(05C4)
Medium Load Iq Level
(low)
Set
n8-78 [Medium Load Id Current]
to the percentage of load current (q-axis current) that
you will apply, where
E5-03 [Motor Rated Current (FLA)] = a setting value of 100%
.
50%
(0 - 255%)
n8-76
(05CD)
Expert
Id Switching Filter Time
Sets the filter time constant for d-axis current reference. Usually it is not necessary to
change this setting.
200 ms
(0 - 5000 ms)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV