304
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
Figure 2.56 Functional Block Diagram of MEMOBUS Multi-function Output
Table 2.53 MEMOBUS MFDO Registers
Register number
(Hex.)
Name
15E0
bit0
MEMOBUS MFDO 1
bit1
MEMOBUS MFDO 2
bit2
MEMOBUS MFDO 3
Note:
•
Refer to
MFDO Setting Values on page 308
for more information about MFDO setting values.
•
When you do not set functions to
H2-40 to H2-42
, set them to
F
.
■
Output of Logical Operation Results of MFDO
This enables the logical operation results of two MFDOs to be output to one MFDO terminal.
Use
H2-60, H2-63, and H2-66 [Term M1-M2 Secondary Function to Term M5-M6 Secondary Function]
to set the
function of the output signal for which logical operations are performed.
Use
H2-61, H2-64, H2-67 [Term M1-M2 Logical Operation to Term M5-M6 Logical Operation]
to set the logical
operation.
Figure 2.57 Functional Block Diagram of Logical Operation Output for MFDO 1
Table 2.54 MFDO Logical Operation Table
Logical Operation Selection
Logical Operation Expression
Logical Operation Notation
H2-61, H2-64, H2-67
0
A=B=1
1
A=1 or B=1
2
A=0 or B=0
3
A=B=0
4
A=B
A=B
5
A != B
6
AND(A, )
7
OR(A, )
8
-
On