YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
Note:
You can disable Auto Restart for faults if you must not restart the machine after the fault.
Table 2.60 List of Faults during which Auto Restart is Available
Fault
Name
Parameters to Disable Auto
Restart
CE
Modbus Communication Error
H5-36
FDBKL
WIRE Break
L5-42
GF
Ground Fault
L5-08
HFB
High Feedback Sensed
L5-41
LF
Output Phase Loss
-
LFB
Low Feedback Sensed
L5-40
LOP
Loss of Prime
L5-51
NMS
Setpoint Not Met
L5-50
oC
Overcurrent
-
oH1
Heatsink Overheat
L5-08
Fault
Name
Parameters to Disable Auto
Restart
oL1
Motor Overload
L5-07
oL2
Drive Overload
L5-07
oL3
Overtorque Detection 1
L5-07
oL4
Overtorque Detection 2
L5-07
ov
Overvoltage
L5-08
PF
Input Phase Loss
-
STPo
Motor Step-Out Detected
-
Uv1
DC Bus Undervoltage
L5-08
VLTS
Thermostat Fault
L5-53
*1
Uv1
is the target for the auto restart process when
L2-01 = 1 or 2 [Power Loss Ride Through Select = Enabled for L2-02 Time or Enabled
while CPU Power Active]
.
Note:
•
The Fault Restart method is limited to the interval time that the drive will use
L5-04 [Interval Method Restart Time]
.
•
When
L5-49 = 1 [Fault Retry Speed Search Select = Enabled]
, the drive will do a speed search when it resets and restarts after a fault.
•
The drive will force the output frequency to zero during the auto-restart interval time.
•
If you remove the Run (or HAND) command during the auto-restart interval time, the drive will immediately detect a fault and reset the
fault.
•
The
LOP [Loss of Prime]
fault uses
Y1-23 [Prime Loss Max Restart Time]
for Auto Restart time. The other faults use
L5-04
for Auto
Restart time.
•
When you enable Thrust or Pre-Charge Modes, the drive will operate them correctly
■
L5-01: Number of Auto-Restart Attempts
No.
(Hex.)
Name
Description
Default
(Range)
L5-01
(049E)
Number of Auto-Restart
Attempts
Sets the number of times that the drive will try to restart.
0
(0 - 10 times)
The drive resets the number of Auto Restart attempts to 0 in these conditions:
•
The drive operates correctly for 10 minutes after a fault restart.
•
When you manually clear a fault after the drive triggers protective functions.
•
When you re-energize the drive.
■
L5-02: Fault Contact at Restart Select
No.
(Hex.)
Name
Description
Default
(Range)
L5-02
(049F)
Fault Contact at Restart
Select
Sets the function that sends signals to the MFDO terminal set for
Fault [H2-xx = E]
while the drive
is automatically restarting.
0
(0, 1)
0 : Active Only when Not Restarting
The drive will only activate fault output when the drive cancels the Auto Restart function.
When you remove the Run command during the time set in
L5-04 [Interval Method Restart Time]
, the drive will
cancel the Auto Restart function. At the same time, the drive will activate the fault output. Refer to
for
more information.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV