142
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
◆
YF: PI Auxiliary Control
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
YF-01
(3F50)
PI Aux Control Selection
Sets the PI Auxiliary Control function.
0 : Disabled
1 : Enabled
0
(0, 1)
YF-02
(3F51)
RUN
PI Aux Control
Transducer Scale
Sets the full scale (10 V or 20 mA) output of the pressure transducer connected to the
analog input terminal programmed for
H3-xx = 27 [PI Aux Control Feedback Level]
.
Note:
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level
Decimal Place Pos]
set the unit and resolution.
145.0
(1.0 - 6000.0)
YF-03
(3F52)
RUN
PI Aux Control Setpoint
Sets the level to which the drive will try to regulate.
Note:
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level
Decimal Place Pos]
set the unit and resolution.
20.0 PSI
(0.0 - 6000.0)
YF-04
(3F53)
RUN
PI Aux Control Minimum
Level
Sets the level below which the drive must be for longer than
YF-05 [PI Aux Control Sleep
Delay Time]
before the drive goes to sleep and turns off all lag pumps.
Note:
•
Set this parameter to 0.0 to disable the function.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level
Decimal Place Pos]
set the unit and resolution.
10.0 PSI
(0.0 - 6000.0)
YF-05
(3F54)
RUN
PI Aux Control Sleep
Delay Time
Sets the length of time that the drive will delay before it goes to sleep after the level is less
than
YF-04 [PI Aux Control Minimum Level]
(when
YF-23 = 1 [PI Aux Ctrl Output Level
Select = Inverse Acting]
) or more than
YF-24 [PI Auxiliary Ctrl Maximum Level]
(when
YF-23 = 0 [Direct Acting]
).
5 s
(0 - 3600 s)
YF-06
(3F55)
RUN
PI Aux Control Wake-up
Level
Sets the level to wake up the drive when the drive after
YF-04 [PI Aux Control Minimum
Level]
or
YF-24 [PI Auxiliary Ctrl Maximum Level]
put the drive to sleep.
Note:
•
Parameter
YF-23 [PI Aux Ctrl Output Level Select]
sets the condition to wake up the
drive.
–
YF-23 = 0 [Direct Acting]
: The PI Aux Feedback must be less than the level set in
this parameter for longer than the time set in
YF-07
to wake up.
–
YF-23 = 1 [Inverse Acting]
: The PI Aux Feedback must be more than the level set
in this parameter for longer than the time set in
YF-07 [PI Aux Control Wake-up
Time]
to wake up.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level
Decimal Place Pos]
set the unit and resolution.
30.0 PSI
(-999.9 - +999.9 PSI)
YF-07
(3F56)
PI Aux Control Wake-up
Time
Sets the time to wake up the drive when the drive after
YF-04 [PI Aux Control Minimum
Level]
or
YF-24 [PI Auxiliary Ctrl Maximum Level]
put the drive to sleep.
Note:
Parameter
YF-23 [PI Aux Ctrl Output Level Select]
sets the condition to wake up the
drive.
•
YF-23 = 0 [Direct Acting]
: The PI Aux Feedback must be less than the level set in
YF-06
for longer than the time set in
YF-07
to wake up.
•
YF-23 = 1 [Inverse Acting]
: The PI Aux Feedback must be more than the level set in
YF-06 [PI Aux Control Wake-up Level]
for longer than the time set in
YF-07
to wake
up.
1 s
(0 - 3600 s)
YF-08
(3F57)
RUN
PI Aux Control Minimum
Speed
Sets the minimum speed at which the drive can run when the PI Auxiliary Control has an
effect on the output speed.
Note:
The drive will use
Y1-06 [Minimum Speed]
and
Y4-12 [Thrust Frequency]
as the
minimum speed when PI Aux Control does not have an effect on the output speed or
when you set
YF-08 < Y1-06 and Y4-12
.
0.00 Hz
(0.00 - 400.00 Hz)
YF-09
(3F58)
RUN
PI Aux Control Low
Level Detect
Sets the level below which the drive must be for longer than
YF-10 [PI Aux Control Low
Lvl Det Time]
to respond as specified by
YF-11 [PI Aux Control Low Level Det Sel]
.
Note:
•
Set this parameter to 0.0 to disable the function.
•
Parameter
YF-10
only applies to when
YF-11 = 2 and 3 [Fault and Auto-Restart
(time set by YF-15)]
.
•
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level
Decimal Place Pos]
set the unit and resolution.
0.0 PSI
(-999.9 - +999.9 PSI)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV