High PI Auxiliary Feedback Level Detection
Table 2.85 Absolute Mode and Delta to Setpoint Mode
Entry Mode
Keypad Display
Description
YF-09
YF-12
Absolute
The values set for
YF-09 and YF-12
represent the
feedback level that will cause a Low PI Auxiliary
Feedback and High PI Auxiliary Feedback. You
can set these parameters as an absolute value.
Delta to Setpoint
When the left-most digit changes to a Δ (delta),
you can set the Low Feedback Level and High
Feedback Level relative to the setpoint.
The effective Low PI Auxiliary Feedback Level is
“
Setpoint -
YF-09
”
, and the effective High PI
Auxiliary Feedback Level is
“
Se
YF-12
”
.
■
YF-01: PI Aux Control Selection
No.
(Hex.)
Name
Description
Default
(Range)
YF-01
(3F50)
PI Aux Control Selection
Sets the PI Auxiliary Control function.
0
(0, 1)
0 : Disabled
1 : Enabled
When
Y1-01 = 3 [Multiplex Mode = Memobus Network]
and
YF-01 = 1
, a staged Lead drive will de-stage as
specified by minimum or maximum PI Auxiliary Feedback Level:
•
A staged Lead drive will de-stage when
U5-16 [PI Aux Ctrl Feedback]
is less than
YF-04 [PI Aux Control
Minimum Level]
for the time set in
YF-05 [PI Aux Control Sleep Delay Time]
.
•
A staged Lead drive will de-stage when
U5-16
is more than
YF-24 [PI Auxiliary Ctrl Maximum Level]
for the time
set in
YF-05
.
■
YF-02: PI Aux Control Transducer Scale
No.
(Hex.)
Name
Description
Default
(Range)
YF-02
(3F51)
RUN
PI Aux Control Transducer
Scale
Sets the full scale (10 V or 20 mA) output of the pressure transducer connected to the analog input
terminal programmed for
H3-xx = 27 [PI Aux Control Feedback Level]
.
145.0
(1.0 - 6000.0)
Note:
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place Pos]
set the unit and resolution.
■
YF-03: PI Aux Control Setpoint
No.
(Hex.)
Name
Description
Default
(Range)
YF-03
(3F52)
RUN
PI Aux Control Setpoint
Sets the level to which the drive will try to regulate.
20.0 PSI
(0.0 - 6000.0)
Note:
Parameters
YF-21 [PI Aux Ctrl Level Unit Selection]
and
YF-22 [PI Aux Level Decimal Place Pos]
set the unit and resolution.