316
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
■
1A: During Reverse
Setting Value
Function
Description
1A
During Reverse
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
Figure 2.69 Reverse Operation Output Time Chart
■
1B: During Baseblock (N.C.)
Setting Value
Function
Description
1B
During Baseblock (N.C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching and does not
make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
■
1C: Motor 2 Selected
Setting Value
Function
Description
1C
Motor 2 Selection
The terminal activates when you select motor 2.
ON : Motor 2 Selection
OFF : Motor 1 Selection
■
1E: Executing Auto-Restart
Setting Value
Function
Description
1E
Executing Auto-Restart
The terminal activates when the Auto Restart function is trying to restart after a fault.
The terminal deactivates when the Auto Restart function automatically resets a fault. The terminal deactivates when
the Auto Restart function detects the fault again because there were too many restart attempts as specified by
L5-01
[Number of Auto Restart Attempts]
.
Note:
Refer to
for more information.
■
1F: Motor Overload Alarm (oL1)
Setting Value
Function
Description
1F
Motor Overload Alarm
(oL1)
The terminal activates when the electronic thermal protection value of the motor overload protective function is a minimum of 90%
of the detection level.
Note:
Refer to
“
L1-01: Motor Overload (oL1) Protection
”
for more information.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV