TOEPYAIHV6002A HV600 Drive Programming
67
Setting Value
Function
Description
Ref.
11E
!Executing Auto-Restart
The terminal deactivates when the Auto Restart function is trying to restart after a fault.
11F
!Motor Overload Alarm
(oL1)
The terminal deactivates when the electronic thermal protection value of the motor overload protective function is a
minimum of 90% of the detection level.
120
!Drive Overheat Pre-
Alarm (oH)
The terminal deactivates when the drive heatsink temperature is at the level set with
L8-02 [Overheat Alarm Level]
.
121
!Safe Torque OFF
The terminal deactivates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly
and when terminals H1-HC and H2-HC are OFF (Open).
ON : Safety circuit fault or RUN/READY
OFF : Safety stop state
12F
!Maintenance
Notification
The terminal deactivates when drive components are at their estimated maintenance period.
Tells the user about the maintenance period for these items:
•
IGBT
•
Cooling fan
•
Capacitor
•
Soft charge bypass relay
130
!During Torque Limit
The terminal deactivates when the torque reference is the torque limit set with
L7 parameters
,
H3-02, or H3-10 [MFAI
Function Selection]
.
137
!During Frequency
Output
The terminal deactivates when the drive outputs frequency.
ON : The drive does not output frequency.
OFF : The drive outputs frequency.
138
!Drive Enabled
This terminal deactivates when the
H1-xx = 6A [Drive Enable]
terminal deactivates.
139
!Watt Hour Pulse Output
Outputs the pulse that shows the watt hours.
13A
!Drive Overheat Alarm
The terminal deactivates when the drive heatsink temperature is at the
L8-02 [Overheat Alarm Level]
setting while
L8-
03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)]
and the drive is running.
13D
!During Speed Search
The terminal deactivates when the drive is doing speed search.
142
!Pressure Reached
The terminal deactivates when the drive is at the Pressure Setpoint.
14A
!During KEB Ride-Thru
The terminal deactivates during KEB Ride-Thru.
14B
!During Short Circuit
Braking
The terminal deactivates during Short Circuit Braking.
Note:
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this function is available only when you use a PM motor.
14C
!During Fast Stop
The terminal deactivates when the fast stop is in operation.
14D
!oH Pre-Alarm Reduction
Limit
The terminal deactivates when
L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)]
and
oH [Heatsink Overheat]
does not clear after the drive decreases the frequency for 10 cycles.
151
!Sequence Timer 1
The terminal deactivates when Sequence Timer 1 is active.
152
!Sequence Timer 2
The terminal deactivates when Sequence Timer 2 is active.
153
!Sequence Timer 3
The terminal deactivates when Sequence Timer 3 is active.
154
!Sequence Timer 4
The terminal deactivates when Sequence Timer 4 is active.
158
!UL6 Underload Detected
The terminal deactivates when the drive detected
UL6 [Underload or Belt Break Detected]
.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV