402
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
■
n8-66: Output Voltage Limit Filter Time
No.
(Hex.)
Name
Description
Default
(Range)
n8-66
(0235)
Expert
Output Voltage Limit Filter
Time
Sets the filter time constant for output voltage control. Usually it is not necessary to change this
setting.
0.020 s
(0.000 - 5.000)
■
n8-74: Light Load Iq Level
No.
(Hex.)
Name
Description
Default
(Range)
n8-74
(05C3)
Light Load Iq Level
Set
n8-48 [Pull-in/Light Load Id Current]
to the percentage of load current (q-axis current) that you
will apply, where
E5-03 [Motor Rated Current (FLA)] = a setting value of 100%
.
30%
(0 - 255%)
Note:
•
If
n8-74
>
n8-75 [Medium Load Iq Level (low)]
, the drive will detect
oPE08 [Parameter Selection Error]
.
•
The change is linear between
n8-74
and
n8-75
and the level of the pull-in current from
n8-48
to
n8-78 [Medium Load Id Current]
.
■
n8-75: Medium Load Iq Level (low)
No.
(Hex.)
Name
Description
Default
(Range)
n8-75
(05C4)
Medium Load Iq Level (low)
Set
n8-78 [Medium Load Id Current]
to the percentage of load current (q-axis current) that you will
apply, where
E5-03 [Motor Rated Current (FLA)] = a setting value of 100%
.
50%
(0 - 255%)
Note:
•
If
n8-74 [Light Load Iq Level]
>
n8-75
, the drive will detect
oPE08 [Parameter Selection Error]
.
•
The change is linear between
n8-74
and
n8-75
and the level of the pull-in current from
n8-48
to
n8-78 [Medium Load Id Current]
.
■
n8-76: Id Switching Filter Time
No.
(Hex.)
Name
Description
Default
(Range)
n8-76
(05CD)
Expert
Id Switching Filter Time
Sets the filter time constant for d-axis current reference. Usually it is not necessary to change this
setting.
200 ms
(0 - 5000 ms)
■
n8-77: Heavy Load Iq Level
No.
(Hex.)
Name
Description
Default
(Range)
n8-77
(05CE)
Heavy Load Iq Level
Set
n8-49 [Heavy Load Id Current]
to the percentage of load current (q-axis current) that you will
apply, where
E5-03 [Motor Rated Current (FLA)] = a setting value of 100%
.
90%
(0 - 255%)
Note:
The change is linear between
n8-75 [Medium Load Iq Level (low)]
and
n8-77
and the level of the pull-in current from
n8-78 [Medium Load
Id Current]
to
n8-49 [Heavy Load Id Current]
.
■
n8-78: Medium Load Id Current
No.
(Hex.)
Name
Description
Default
(Range)
n8-78
(05F4)
Medium Load Id Current
Sets the level of the pull-in current for mid-range loads.
0%
(-200 - +200%)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV