YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
113
1.18
U: Monitors
◆
U1: Operation Status Monitors
No.
(Hex.)
Name
Description
MFAO Signal Level
U1-01
(0040)
Frequency Reference
Shows the frequency reference value. Parameter
o1-03 [Keypad Display Unit Selection]
sets the
display units.
Unit: 0.01 Hz
10 V = Maximum frequency
(0 V to +10 V)
U1-02
(0041)
Output frequency
Shows the output frequency. Parameter
o1-03 [Keypad Display Unit Selection]
sets the display units.
Unit: 0.01 Hz
10 V = Maximum frequency
(0 V to +10 V)
U1-03
(0042)
Output Current
Shows the output current.
The keypad shows the value of
U1-03
in amperes (A). When you use serial communications to show
the monitor, the current is
“
8192 = drive rated current (A)
”
. Use the formula:
“
Numerals being
displayed / 8192 × drive rated current (A)
”
to use the serial communication current value shown in
the monitor.
Unit: Determined by the drive model.
•
0.01 A: 2011 to 2046, 4005 to 4014
•
0.1 A: 2059 to 2273, 4021 to 4302
10 V = Drive rated current
U1-04
(0043)
Control Method
Shows the drive control method.
0 : V/f Control
5 : PM Open Loop Vector
8 : EZ Vector Control
No signal output available
U1-05
(0044)
Motor Speed
Shows the detected motor speed. Parameter
o1-03 [Keypad Display Unit Selection]
sets the display
units.
Unit: 0.01 Hz
10 V = Maximum frequency
(0 V to +10 V)
U1-06
(0045)
Output Voltage Ref
Shows the output voltage reference.
Unit: 0.1 V
208 V class: 10 V = 200
Vrms
480 V class: 10 V = 400
Vrms
U1-07
(0046)
DC Bus Voltage
Shows the DC bus voltage.
Unit: 1 V
208 V class: 10 V = 400 V
480 V class: 10 V = 800 V
U1-08
(0047)
Output Power
Shows the internally-calculated output power.
When you change
A1-02 [Control Method Selection]
, it will also change the signal level of the
analog output.
•
A1-02 = 0: Drive capacity (kW)
•
A1-02 = 5:
PM Motor Rated Power [E5-02]
(kW)
•
A1-02 = 8:
Motor Rated Power [E9-07]
(kW)
Unit: Determined by the drive model.
•
0.01 kW: 2011 to 2046, 4005 to 4014
•
0.1 kW: 2059 to 2273, 4021 to 4302
10 V: Drive capacity (motor
rated power) kW
(-10 V to +10 V)
U1-09
(0048)
Torque Reference
Shows the internal torque reference value.
Unit: 0.1%
10 V = Motor rated torque (0
V to +10 V)
U1-10
(0049)
Input Terminal Status
Shows the status of the MFDI terminal where 1 = (ON) and 0 = (OFF).
For example,
U1-10
shows
“
00000011
”
when terminals S1 and S2 are ON.
bit0 : Terminal S1 (MFDI 1)
bit1 : Terminal S2 (MFDI 2)
bit2 : Terminal S3 (MFDI 3)
bit3 : Terminal S4 (MFDI 4)
bit4 : Terminal S5 (MFDI 5)
bit5 : Terminal S6 (MFDI 6)
bit6 : Terminal S7 (MFDI 7)
bit7 : Not used (normal value of 0).
No signal output available
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV