L8-97: Carrier Freq Reduce during OH
No.
(Hex.)
Name
Description
Default
(Range)
L8-97
(3104)
Carrier Freq Reduce during
OH
Sets the function to decrease carrier frequency during oH pre-alarm.
0
(0, 1)
Note:
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this parameter is available only when
E9-01 = 0 [Motor Type Selection = Induction
(IM)]
.
0 : Disabled
1 : Enabled
◆
L9: Drive Protection 2
L9 parameters
are used to configure the protection function used to detect cooling fan faults.
■
L9-16: FAn1 Detect Time
No.
(Hex.)
Name
Description
Default
(Range)
L9-16
(11DC)
Expert
FAn1 Detect Time
Sets the detection time for
FAn1 [Drive Cooling Fan Fault]
. Yaskawa recommends that you do not
change this parameter value.
4.0 s
(0.0 - 30.0 s)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV