360
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
■
L2-30: KEB Zero Speed Operation
No.
(Hex.)
Name
Description
Default
(Range)
L2-30
(045E)
Expert
KEB Zero Speed Operation
Sets the operation when the output frequency decreases below the zero level (DC braking injection
starting frequency) during KEB deceleration.
0
(0, 1)
0 : Baseblock
1 : DC/SC Braking
Does DC injection braking and short circuit braking as specified by
b2-04 [DC Inject Braking Time at Stop]
and
b2-
13 [Short Circuit Brake Time @ Stop]
.
■
L2-31: KEB Start Voltage Offset Level
No.
(Hex.)
Name
Description
Default
(Range)
L2-31
(045D)
Expert
KEB Start Voltage Offset
Level
Sets the KEB start voltage offset.
Determined by A1-02
(208 V Class: 0 - 100 V,
480 V Class: 0 - 200 V)
The drive uses this formula to calculate the KEB start voltage:
KEB start voltage =
L2-05 [Undervoltage Detect Level (Uv1)]
+
L2-31
◆
L3: Stall Prevention
L3 parameters
set the Stall Prevention function and overvoltage suppression function.
■
Stall Prevention
If the load is too heavy or the acceleration and deceleration times are too short, the motor can slip too much because it
cannot work at the same rate as the frequency reference. If the motor stalls during acceleration, current increases as
the slip increases to cause an
oC [Overcurrent]
,
oL2 [Drive Overload]
, or
oL1 [Motor Overload]
and the drive will
stop. If the motor stalls during deceleration, too much regenerative power will flow back into the DC bus capacitors
and cause the drive to fault out from
ov [Overvoltage]
and stop the drive.
The stall prevention function will let the motor get to the set speed without stalling and it is not necessary for you to
change the acceleration or deceleration time settings. You can set a separate stall prevention functions for
acceleration, operating at constant speeds, and deceleration.
■
Overvoltage Suppression Function
This function decreases the regenerative torque limit and increases the output frequency when the DC bus voltage
increases to prevent
ov
. This function can drive loads with cyclic regenerative operation, for example punch presses
or other applications with repeated crank movements. When you use this function, set
L3-11 = 1 [Overvoltage
Suppression Select = Enabled]
.
The drive adjusts the regenerative torque limit and the output frequency during overvoltage suppression to make sure
that the DC bus voltage is not more than the level set in
L3-17 [DC Bus Regulation Level]
.
Set these parameters as necessary when you use the overvoltage suppression function:
•
L3-20 [DC Bus Voltage Adjustment Gain]
•
L3-21 [OVSuppression Accel/Decel P Gain]
•
L3-24 [Motor Accel Time @ Rated Torque]
•
L3-25 [Load Inertia Ratio]
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV