YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
65
Setting Value
Function
Description
Ref.
100
!During Run
The terminal deactivates when you input a Run command and when the drive is outputting voltage.
ON : Drive is stopping
OFF : Drive is running
101
!Zero Speed
The terminal deactivates when the output frequency <
E1-09 [Minimum Output Frequency]
.
Note:
Parameter
E1-09
is the reference in all control methods.
ON : Output frequency ≥ value of
E1-09
.
OFF : Output frequency < value of
E1-09
.
102
!Speed Agree 1
The terminal deactivates when the output frequency is in the range of the frequency reference ±
L4-02 [Speed Agree
Detection Width]
.
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency does not align with the frequency reference although the drive is running.
OFF : The output frequency is in the range of
“
frequency reference ±
L4-02
”
.
103
!User-Set Speed Agree 1
The terminal deactivates when the output frequency is in the range of
L4-01 [Speed Agree Detection Level]
±
L4-02
[Speed Agree Detection Width]
and in the range of the frequency reference ±
L4-02
.
Note:
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the
forward/reverse detection level.
ON : The output frequency is not in the range of
“
L4-01
±
L4-02
”
or the range of frequency reference ±
L4-02
.
OFF : The output frequency is in the range of
“
L4-01
±
L4-02
”
and the range of frequency reference ±
L4-02
.
104
!Frequency Detection 1
The terminal activates when the output frequency >
“
L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree
Detection Width]
”
. After the terminal activates, the terminal stays activated until the output frequency is at the value of
L4-01
.
Note:
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the
forward/reverse detection level.
ON : The output frequency >
“
L4-01
+
L4-02
”
.
OFF : The output frequency <
L4-01
, or the output frequency ≤
“
L4-01
+
L4-02
”
105
!Frequency Detection 2
The terminal deactivates when the output frequency >
L4-01 [Speed Agree Detection Level]
. After the terminal
deactivates, the terminal stays deactivated until the output frequency is at the value of
“
L4-01
-
L4-02 [Speed Agree
Detection Width]
”
.
Note:
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the
forward/reverse detection level.
ON : The output frequency <
“
L4-01
-
L4-02
”
, or the output frequency ≤
L4-01
OFF : The output frequency >
L4-01
106
!Drive Ready
The terminal deactivates when the drive is ready and running.
107
!DC Bus Undervoltage
The terminal deactivates when the DC bus voltage or control circuit power supply is at the voltage set in
L2-05
[Undervoltage Detection Lvl (Uv1)]
or less. The terminal also deactivates when there is a fault with the DC bus
voltage.
ON : The DC bus voltage >
L2-05
OFF : The DC bus voltage ≤
L2-05
108
!During Baseblock (N.O.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock.
109
!Frequency Reference
from Keypad
Shows the selected frequency reference source.
ON : Parameter
b1-01 [Frequency Reference Selection 1]
is the frequency reference source.
OFF : The keypad is the frequency reference source.
10B
!Torque Detection 1 (N.
O.)
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque >
L6-02 [Torque Detection Level 1]
, or <
L6-02
for longer than the time set with
L6-
03 [Torque Detection Time 1]
.
10C
!Frequency Reference
Loss
The terminal deactivates when the drive detects a loss of frequency reference.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV